2-2 Sun Fire V120 and Netra 120 Server User’s Guide December 2001
2.1 Operating Power Limits and Ranges
The table below gives operating and power information for the Sun Fire V120 and
Netra 120 servers.
*For both servers, the in-rush currentdecays to the normal operating current in less than
200 milliseconds. The in-rushdecaying peaks last for less than 3 milliseconds in each half
cycle.
Note – The figures for the maximum operating current areprovided to help you
specify the fusing and cabling you need to deliver power to your equipment.
However,these figures represent “worst-case” scenarios. Such occurrences are
unlikely in a real installation.
TABLE2-1 Operating Power Limits and Ranges for Sun Fire V120 and Netra 120 Servers
Description SunFire V120 Server (AC power) Netra120 Server (DC power)
Maximum operating
current 2A@ 90 VAC 4A @ 40 VDC
Maximum in-rush
current(cold start) 20A peak upon a restart
performed 60 seconds or more
after the removalof AC power
20A peak upon a restart
performed 60 seconds or more
after the removalof DC power
Maximum in-rush
current(warm start) 40A peak upon a restart
performed less than 60 seconds
but morethan 200 milliseconds
after the removalof AC power
40A peak upon a restart
performedless than 60 seconds
butmore than 200 milliseconds
after the removalof DC power
Maximum in-rush
current(hot start) 100A peak upon a restart
performed less than 200
milliseconds after the removal
of AC power
100A peak upon a restart
performed less than 200
milliseconds after the removal
of DC power
Operating input
voltage range 90-264 Vrms 40 to 75 VDC
Voltagefrequency
range 47-63 Hz DC
Power factor 0.8 to 1.0 Notapplicable
BTU rating 550 BTU 550 BTU