Chapter 3 Using DC Power 3-3
3.2 Assembling the DC Power Connectors
The Netra 120 server has a dedicated connector kit; this section explains how to use
it.

3.2.1 The Insulated Conductors You Need to Use

The insulated conductors you use must have the following characteristics:
Material: tinned copper (multistranded)
Size: 12 AWG(2.5 mm2) (maximum)
Rating:
300 vrms (minimum)
75OC
Low-smoke fume (LSF)
Fire resistance:
VW-1
GR63-CORE compliant
Youneed two supply conductors:
One -48V (or -60V) DC supply conductor (return, RTN)grounded at source
One DC supply conductor (- minus)
Finally,you need one power supply unit (PSU) ground conductor.

3.2.2 Assembling the DC Input Power Cable

1. Determine how many DC input power cables you will need from each DC power
source.
2. Turn off power to the DC power source through the circuit breakers.
Caution – Do not proceed with these instructions until you have turned off the
power to the DC power source through the circuit breakers.
3. Take a DC connector from the ship kit.
4. Locate the Supply and Return wires (and the PSU Ground, if you are using it)
comingfrom the DC power sourcethat you intend touse in the connection toyour
server: