12.3 External Connections

The terminal layout of external connection TB1 is shown in Table 8.

Table 8 External Connections.

No.

I/O

Signal Name

Operation

1

Output

Low Battery

Close at Low Battery

2

Output

Backup Operation

Close while Backup Operation

3

Output

Fault

Close by Faults

4

Output

Inverter Supply

Close during Normal Operation

5

Output

Warning

Close by Warnings

6

Input

P24

 

7

Input

Remote Run

Close to run UPS

8

Input

P24

 

9

Input

Remote Stop

Close to stop UPS

10

Output

Bypass Supply

Close during Bypass Operation

11

Output

Output Signal Ground

(Ground for pin #1~5 and #10)

12

Input

P24

Battery’s

13

Input

Battery Overheat

Overheat B-contact

14

Output

 

Bypass Breaker

15

Output

52C Trip Signal

Shunt Trip Signal by EPO

16

Output

 

Battery Breaker shunt trip

17

Output

72B Trip Signal

by EPO or Battery shutdown

18

Output

 

Battery breaker’s

19

Output

72B Aux. Contact

Auxiliary A-contact

The UPS, the battery cabinet and the bypass breaker should be wired as shown in Figure 11.

 

 

 

 

Power source

 

Jumper wire if battery

 

 

 

 

 

 

 

 

 

 

OH is not applied.

 

 

 

TC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Bypass

Bypass Breaker

 

 

Input

 

 

 

10

 

 

 

11

 

 

 

12

 

 

 

13

 

Power source

 

14

 

 

 

for trip coil

 

15

 

 

 

 

 

16

 

 

 

17

 

 

TC

18

 

 

19

To DC

Overheat

 

TB1

B-contact

 

Input

 

 

 

 

 

Auxiliary A-

contact

< UPS Cabinet >

< Battery Cabinet >

Figure 11 Connection among UPS, battery cabinet & bypass breaker.