16. UPS Specifications

16.1 General Specification

Terms

Specification

Remarks

 

 

 

Conforming Standard

UL1778-2001

UL, cUL, IEC

 

 

 

Ambient Temperature

0°~40° C ( 32°~104° F)

 

 

 

 

Relative Humidity

30% ~ 90%

Non-condensing

 

 

 

Altitude

< 1,000m ( < 3,280ft )

 

 

 

 

Insulation Resistance

3M￿

With 500V-Megger

 

 

 

Insulation withstanding

AC 2kV – 1min.

Main Circuit

voltage

AC 1.5kV – 1min.

External Interface

 

AC 500V – 1min.

Electronic Circuit

 

 

 

Audible Noise

68dB(150/225kVA), 72dB(300kVA)

1m (39”) away from front

 

 

 

16.2 Mechanical Specification

Rated Capacity

150kVA

225kVA

300kVA

 

 

 

 

Cabinet Protection Conformity

 

IEC298 IP20 ( * )

 

 

 

 

 

Exterior Paint

 

2.8Y7.7/0.3

 

 

 

 

 

Panel Thickness Front

 

1.6mm (1/16”)

 

~

Back / Side / Top

 

1.2mm (3/64”)

 

~

Bottom

 

3.2mm ( 1/8”)

 

 

 

 

 

Input / Output cabling entrance

Bottom

Top

 

 

 

 

Ground / Control wiring entrance

Bottom

Top

 

 

 

 

Clearance in Front

 

1,100mm (43” 7/16)

 

~ in Back and Side

 

0mm (0”)

 

~ on Top

 

400mm (15” 3/4)

 

 

 

 

 

Outline Dimension (Width)

1,400mm (55” 1/8)

1950mm (76” 3/4)

 

(Depth)

800mm (31” 1/2)

900mm (35” 7/16)

 

(Height)

2,000mm (78” 3/4)

2,000mm (78” 3/4)

 

 

 

 

 

Weight

 

1,200kg (2,640lbs)

1,500kg (3,300lbs)

2,000kg (4,400lbs)

 

 

 

 

Floor loading per footprint

1,071 kg/m2

1,339 kg/m2

1,139 kg/m2

 

 

( 219 lbs/ft2)

( 274 lbs/ft2)

( 233 lbs/ft2)

 

 

 

 

Heat Rejection

9,550 kcal/h

14,370 kcal/h

19,190 kcal/h

 

 

( 37,914 BTU/h)

( 57,049 BTU/h)

( 76,184 BTU/h)

 

 

 

 

 

(*) IP20 refers to foreign objects entrance and prevents objects of 12mm-diameter(15/32”) or larger.

59

Page 60
Image 60
Toshiba G8000 Series operation manual UPS Specifications, General Specification, Mechanical Specification