Toshiba G8000 Series operation manual Stopping procedure, Move #72B to ‘OFF’ Position

Models: G8000 Series

1 63
Download 63 pages 16.31 Kb
Page 47
Image 47

*To change from Bypass to UPS supply, follow the procedure step #5 in Table 13. If the AC switch does not function, contact Toshiba or authorized representatives.

14.3.3Stop

Table 15 shows the procedure to stop the UPS.

Table 15 - Stopping procedure.

Step

Procedure

 

LCD/LED Status

 

1

 

 

BYPASS

 

 

 

 

 

 

 

 

 

 

 

 

AC-VO

480[V]

 

 

 

 

 

AC- I O

50[%]

 

 

 

 

 

PRESS ‘UPS’ SWITCH

 

 

Transfer to Bypass

￿

~

~

UPS

 

 

supply as described in

AC INPUT

CONVERTER

INVERTER

 

 

 

Table 14.

 

FLOAT CHARGE

 

AC

￿

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

 

 

UPS LED is off and BYPASS LED is on.

 

2

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

 

 

MOVE #72B TO ‘OFF’ POSITION

 

 

Turn off the DC input

￿

~

~

UPS

 

 

 

 

 

 

breaker, and, press the

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

 

“STOP” button for 0.5

 

FLOAT CHARGE

 

AC

￿

 

sec at least.

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

 

 

BATTERIES LED is off and INVERTER LED flashes then

 

 

off.

 

 

 

 

 

 

FLOAT CHARGE LED and CONVERTER LED are off.

46

Page 47
Image 47
Toshiba G8000 Series operation manual Stopping procedure, Move #72B to ‘OFF’ Position