14.3.5 Changing Between Float Charge and Equalize Charge

This section shows the procedure to change the recharge mode between float charge and equalize charge.

(1) Table 17 shows the procedure to change from float charge to equalize charge.

Table 17 - Change From Float Charge to Equalize Charge.

Step

Procedure

LCD/LED Status

 

 

1

Make sure that the

 

 

 

 

 

FLOAT CHARGE LED

UPS SUPPLY

 

 

 

is On.

AC-VO

480[V]

 

 

 

 

 

 

 

 

AC- I O

50[%]

 

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

2

Press FLOAT/EQUAL

 

 

 

 

 

button for 0.5 sec.

UPS SUPPLY

 

 

 

Change completed.

AC-VO

480[V]

 

 

 

 

AC- I O

50[%]

 

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

EQUAL CHARGE LED is On; FLOAT CHARGE LED is Off.

*In equalize charge mode, the battery is charged for a programmed period at a specified voltage (depending on the battery spec) rather than the float charge, in order to prevent voltage deviations among battery cells. This should be done once every six months if possible.

The G8000 UPS has an automatic function to perform the equalize recharge after battery backup operation.