15.2.3 Fault Messages

Figure 19 show the locations for fault detection. Tables 22 through 26 list the fault messages described in section "Fault Data Screen." The content and display text for the fault and warning messages are in Tables 22 through 26. The UPS unit can be shipped with different protective configurations from the standard shown in Figure 19, if specified by the customer. See the protective configuration indicated on the single line diagram for each UPS.

47S

95S

27S

59S

52R

 

 

 

 

59I

 

 

51I

 

27I

45

INVERTER

 

 

 

 

 

83MC1

49

5E

80PS

30ST

48

26

Chopper

76C

80B1 80B2

95C

59C

47C

27C

30U

76

26B

83MC2

71F

UPS

83BF

Figure 19 - Protective Detector Locations.

 

 

 

Table 22 - Fault (Trip).

 

 

 

 

 

#

Item

LCD Message

 

Description

Indication

 

 

 

 

 

 

 

 

 

 

1

71F

FUSE BLOWN

 

AC or DC Main circuit fuse blown.

 

 

 

 

 

2

30ST

(No indication)

 

An error occurred in the main control

 

microprocessor (CPU).

 

 

 

 

 

 

 

 

 

3

80PS

CONT. PS. ERR

 

The control power supply voltage failed.

 

 

 

 

 

4

80B2

BATT. UV

 

Battery voltage is below cutoff voltage.

 

 

 

 

 

5

48

STARTUP ERR

 

Startup was not completed in a time frame.

 

 

 

 

 

6

76

DC OC

 

Over-current in DC circuit.

 

 

 

 

 

7

26

OVER HEAT

 

Temp High in the cabinet.

 

 

 

 

 

8

5E

EMG.STOP

 

An emergency stop was activated by the external

 

contact.

 

 

 

 

 

 

 

 

 

54