16.3 Electrical Specification
Rated Capacity
150kVA (120kW)
225kVA (180kW)
300kVA (240kW)
AC Input |
|
|
|
|
|
|
|
|
| ||
Input Voltage | 480V ( +10% ~ | ||||
|
|
|
|
|
|
Input Frequency |
|
| 60Hz ±5% |
| |
|
|
|
| ||
Input Power Factor | 0.95 ~ 1.00 Lagging ( at 100% Load ) | ||||
|
|
|
|
|
|
Current Harmonic Distortion |
| 6% Maximum ( at 100% Load ) |
| ||
|
|
|
|
|
|
Input Capacity Required | 154kVA |
| 232kVA |
| 309kVA |
|
|
|
|
|
|
Circuit Breaker Rating at 480V input | 225A Trip |
| 350A Trip |
| 450A Trip |
|
|
|
|
|
|
DC Input |
|
|
|
|
|
|
|
|
|
| |
Voltage Window |
|
| 288 ~ 414 V |
| |
|
|
|
|
| |
Recharge Voltage Regulation |
| ± 1.5% |
|
| |
|
|
|
|
|
|
AC Output |
|
|
|
|
|
|
|
|
| ||
Output Voltage |
| 480/277V ± 1%, |
| ||
|
|
|
|
| |
Output Power Factor |
|
| 0.8 Lagging |
| |
|
| ||||
Voltage Distortion | 3% with 100% Linear Load / 5% with | ||||
|
|
|
|
| |
Transient Voltage Regulation |
| < ± 2% |
|
| |
|
|
|
|
| |
Transient Settling Time |
|
| < 50msec |
| |
|
|
|
|
| |
Crest Factor |
| < 2.0 |
|
| |
|
| ||||
Output Frequency | 60Hz ± 0.01% ( at | ||||
|
|
|
|
| |
Synchronous window to the utility line |
|
| 59Hz ~ 61Hz |
| |
|
|
|
|
| |
Frequency Slew Rate |
|
| 1Hz/Sec |
| |
|
| ||||
Over Load Rating | |||||
|
|
|
|
|
|
60