13.2.1 Normal Display

The Normal Display screen indicates the UPS operational status and provides 15 screens: an operation guidance screen, an operation mode screen and 13 screens of measured data. Table 10 shows these screens page by page.

 

 

 

 

Table 10 - Normal Display.

 

 

 

 

 

 

 

No.

LCD Screen

 

 

 

Description

 

 

 

 

 

1

Operation Guidance

 

 

(Example 1)

 

 

 

Shows the UPS status at the top and guidance

 

 

 

 

 

 

 

 

 

 

 

message or measured data underneath.

 

 

BYPASS

 

 

 

 

PRESS ‘RUN’ SWITCH

 

(Example 1)

 

 

 

 

 

 

 

 

 

 

Shows a guidance message at start up.

 

 

 

 

 

 

 

 

(Example 2)

 

 

 

(Example 2)

 

 

 

 

Shows the output voltage and current after start

 

 

UPS SUPPLY

 

 

AC-VO

480[V]

 

up.

 

 

AC- I O

50[%]

 

 

 

 

 

 

 

 

Voltage (example)

 

 

 

 

 

 

Current ratio (example)

 

 

 

 

 

2

Operation Mode

 

 

(Example)

 

 

 

Shows the UPS Operation mode.

 

 

 

 

 

 

 

 

OPERATION MODE

 

 

 

 

 

 

 

 

 

NORMAL OPERATION MODE

 

 

 

 

 

SYNC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Measurement screen #1

 

 

 

 

 

Output voltage

Shows the output voltage between lines.

 

 

 

 

 

 

 

 

O/P VOLTAGE

 

 

 

VOLT.

480[V]

 

 

 

 

FREQ.

60.0[Hz]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Measurement screen #2

 

 

 

Output current (RMS)

Shows the output current RMS (%) for each

 

 

 

 

 

 

 

 

 

 

phase.

 

 

O/P CURRENT (r.m.s)

 

 

U

50[%]

 

 

 

 

V

50[%]

 

 

 

 

W

50[%]

 

 

 

 

 

 

 

 

 

38