14.3.4 Complete Shutdown

This section shows the procedure to turn off the control power and shut down the UPS completely.

Table 16 - Complete Shutdown.

Step

Procedure

 

LCD/LED Status

 

 

 

 

 

 

1-3

Same as steps 1-3 in "Stop" section.

 

 

 

 

 

 

 

 

4

Scroll the LCD screen

 

 

 

 

 

DC INPUT

 

 

 

to see the DC INPUT

 

 

 

 

and make sure DC bus

 

DC-V

0[V]

 

 

voltage is 0V.

 

BATT-V

0[V]

 

 

 

 

BATT- I

0[A]

 

 

 

 

 

 

 

 

 

 

 

 

5

*Turn off the control

Nothing is displayed on the LCD and all LED’s are off.

 

power supply switch

 

 

 

 

 

(8A).

 

 

 

 

 

 

 

 

 

6

Turn off all breakers at

(Shutdown is completed and UPS is isolated.)

 

AC output, Bypass

 

 

 

 

 

Input and AC Output.

 

 

 

 

 

 

 

 

 

 

*This operation is different from the displayed instruction on the screen. Be sure to perform the procedure specified here.