→Procedure completed.
BYPASS
PRESS ‘RUN’ SWITCH
~ | ~ | UPS | |
|
| ||
AC INPUT | CONVERTER | INVERTER |
|
| FLOAT CHARGE |
| AC |
|
|
| |
BATTERIES | EQUAL CHARGE |
| SWITCH |
| DISCHARGE |
|
|
BYPASS
BYPASS INPUT
AC OUTPUT
14.3.4 Complete Shutdown
This section shows the procedure to turn off the control power and shut down the UPS completely.
Table 16 - Complete Shutdown.
Step | Procedure |
| LCD/LED Status | ||
|
|
|
|
|
|
Same as steps |
|
| |||
|
|
|
|
|
|
4 | Scroll the LCD screen |
|
|
|
|
| DC INPUT |
|
| ||
| to see the DC INPUT |
|
|
| |
| and make sure DC bus |
|
| 0[V] |
|
| voltage is 0V. |
|
| 0[V] |
|
|
|
| BATT- I | 0[A] |
|
|
|
|
|
| |
|
|
|
|
|
|
5 | *Turn off the control | Nothing is displayed on the LCD and all LED’s are off. | |||
| power supply switch |
|
|
|
|
| (8A). |
|
|
|
|
|
|
|
|
| |
6 | Turn off all breakers at | (Shutdown is completed and UPS is isolated.) | |||
| AC output, Bypass |
|
|
|
|
| Input and AC Output. |
|
|
|
|
|
|
|
|
|
|
*This operation is different from the displayed instruction on the screen. Be sure to perform the procedure specified here.
47