Table 13 - Startup Procedures (Cont’d).

3

Press the "RUN" button

 

 

 

 

 

for 0.5 sec.

BYPASS

 

 

 

 

 

UPS STARTING

 

 

 

 

WAIT FOR A WHILE

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

CONVERTER LED is on and INVERTER LED flashes.

4

Turn on the DC input

 

 

 

 

 

breaker.

BYPASS

 

 

 

 

 

MOVE #72B TO ‘ON’ POSITION

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

BATTERIES LED is on.

 

 

5

Press the “UPS” button

 

 

 

 

 

for 0.5 sec.*

UPS SUPPLY

 

 

 

 

AC-VO

480[V]

 

 

 

This completes UPS

AC- I O

50[%]

 

 

 

 

 

 

 

 

startup procedure.

 

 

 

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

 

BYPASS LED is off and UPS LED is on.

 

* Notes:

-If the AC switch dose not function, contact Toshiba or authorized representatives.

-If the bypass power source is out of specification, this operation will be inhibited. In order to switch manually, press the “UPS” button for 5 seconds or more.