Table 9 - LCD/LED Legend.

 

 

 

 

No.

Name

 

Function

 

 

 

 

11

 

 

LCD indicates operation procedure, measured data and

 

LCD

 

warnings/faults.

 

 

 

 

 

 

Detailed in the section titled "LCD Display."

 

 

 

 

12

UPS SUPPLY LED

 

Turned on while the inverter is on. Flashes during start-up

 

 

or stop procedure.

 

 

 

 

 

 

 

13

WARNING LED

 

Normally off. Turned on with warnings, flashes with AC

 

 

input abnormality.

 

 

 

 

 

 

 

14

FAULT LED

 

Normally off. Turned on with faults.

 

 

 

 

15

AC INPUT LED

 

Normally on with regular AC input. Flashes with AC

 

 

input under-voltage (85%).

 

 

 

 

 

 

 

16

RECTIFIER LED

 

Turned on after DC caps are charged up through the

 

 

rectifier.

 

 

 

 

 

 

 

17

INVERTER LED

 

Flashes during start-up or stop procedure. Turned on after

 

 

the inverter starts up, and during available.

 

 

 

 

 

 

 

18

AC OUTPUT LED

 

Turned on with AC output fed by either the bypass or

 

 

inverter sources.

 

 

 

 

 

 

 

19

BATTERY LED

 

Turned on with battery connected. (Aux-contact on)

 

 

 

 

20

FLOAT CHARGE LED

 

Turned on during float charge.

 

 

 

 

21

EQUALIZE CHARGE LED

 

Turned on during equalize charge or protection charge

 

 

with battery OH contact open.

 

 

 

 

 

 

 

22

DISCHARGE LED

 

Turned on during battery discharge.

 

 

 

 

23

BYPASS INPUT LED

 

Normally on with regular bypass input. Flashes with bypass

 

 

under-voltage (85%).

 

 

 

 

 

 

 

24

UPS LED

 

Turned on during UPS Supply.

 

 

 

 

25

BYPASS LED

 

Turned on during Bypass Supply.

36

Page 37
Image 37
Toshiba G8000 Series operation manual LCD/LED Legend, Name Function