Start-Up

Analog Inputs

See Table 28 for a complete description of analog inputs.

Table 28. Analog inputs

Analog input

Terminal

Function

Range

ZN010

ZN510

ZN520

 

 

 

 

 

 

 

Zone

TB3-1

Space temperature input

5° to 122°F (-15° to 50°C)

 

 

 

 

 

 

 

Ground

TB3-2

Analog ground

N/A

 

 

 

 

 

 

 

Set

TB3-3

Setpoint input

40° to 115°F (4.4° to 46.1°C)

 

 

 

 

 

 

 

Fan

TB3-4

Fan switch input

4821 to 4919 W (Off)

 

 

 

2297 to 2342 W (Auto)

 

 

 

 

 

 

10593 to 10807 W (Low)

 

 

 

 

 

 

15137 to 16463 W (High)

 

 

 

 

 

 

 

 

 

 

Ground

TB3-6

Analog ground

N/A

 

 

 

 

 

 

 

Analog Input 1

J3-1

Entering water temperature

-40° to 212°F (-40° to 100°C)

 

J3-2

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 2

J3-3

Discharge air temperature

-40° to 212°F (-40° to 100°C)

 

J3-4

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 3

J3-6

Fresh air temp/generic temp

-40° to 212°F (-40° to 100°C)

 

 

 

 

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 4

J3-7

Universal Input

0 – 100%

 

 

 

 

Generic 4-20 ma

0 – 100%

 

 

 

 

 

Humidity

0 – 2000ppm

 

 

 

 

 

CO2

 

 

 

 

 

 

 

 

 

 

 

Ground

J3-8

Analog ground

N/A

 

 

 

 

 

 

 

 

 

Ground

J3-9

Analog ground

N/A

 

 

Notes:

1.The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10KW thermistors.

2.Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board.

3.Changeover units include an entering water temperature sensor.

Binary Outputs

Binary outputs are configured to support the following:

Two fan stages (when one or two fan stages are present, J1-2 can be configured as exhaust fan)

One hydronic cooling stage

One hydronic heating stage (dehumidification requires this to be in the reheat position)

One DX cooling stage

One or two-stage electric heat (dehumidification requires this to be in the reheat position)

Face and bypass damper

Modulating fresh air damper (Tracer™ ZN520 only)

One-stage baseboard heat