Diagnostics

Table 39. Tracer ZN010 and ZN510 test sequence for 1-heat/1-cool configurations

 

 

Fan

Cool output(a)

Heat output

Damper

Steps

J1-1, J1-3

J1-

J1-

J1-

 

 

 

 

 

 

1.

Off

Off

Off

Off

Closed

 

 

 

 

 

 

2.

Fan high

High

Off

Off

Closed

 

 

 

 

 

 

3.

Exhaust fan

(b)

Off

Off

Closed

 

 

 

 

 

 

4.

Fan

Low

Off

Off

Closed

 

 

 

 

 

 

5.

Cool

High

On

Off

Closed

 

 

 

 

 

 

6.

Heat

High

Off

On

Closed

 

 

 

 

 

 

7.

Two-position damper(c)

High

Off

Off

Open

8.

Exit

(d)

 

 

 

Note: The 2-position damper energizes during this step if the controller is configured for a 2-position damper.

(a)At the beginning of step 2, the controller attempts to clear all diagnostics.

(b)Tracer™ ZN010 and ZN510 have a binary output default as “none” on J1-X from the factory. If the unit has a 2-speed fan, step 3 will energize the low fan speed. If the unit has a single speed fan, step 3 will continue to energize the high fan speed. This binary output can be reconfigured as an exhaust fan, with the use of Rover™ software.

(c)After the fresh air damper step, the test sequence performs the exit step.This initiates a reset and attempts to return the controller to normal operation.

(d)For all 1-heat/1-cool applications including 2-pipe changeover, the cooling and heat test stage energize. This occurs even though during normal 2-pipe changeover operation binary output controls the unit valve for both cooling and heating.

Table 40. Tracer ZN520 test sequence

 

 

 

 

Main

Electric heat or Fresh air

 

 

 

 

 

 

 

Fan

valve

aux. valve

damper

Generic/baseboard heat

 

 

 

 

 

 

 

 

 

 

 

Step

J1-1

J1-2

J1-3

J1-5

J1-6

J1-9

J1-10

J1-11

J1-12

TB4-1

 

 

 

 

 

 

 

 

 

 

 

 

1.

Off(a)

Off

Off

Off

Off

On

Off

aux: on

Off

On

Off

 

 

 

 

 

 

EH: off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Fan high(b)

High

Off

Off

Off

Off

Off

Off

Off

Off

Off

3.(c)

Off

 

Off

Off

Off

Off

Off

Off

Off

Off

4.

Fan low

Off

Off

Low

Off

Off

Off

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

 

 

5.

Main open

High

Off

Off

On

Off

Off

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

 

 

6.

Main close, EH1 on

High

Off

Off

Off

On

On

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

 

 

7.

Aux. open

High

Exh(d)

Off

Off

Off

On

Off

Off

Off

Off

 

 

EH1 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.

Aux. close, damper open

High

Off

Off

Off

Off

Off

On

On

Off

Off

 

 

 

 

 

 

 

EH1 off

EH2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.

Damper close

High

Off

Off

Off

Off

Off

Off

Off

On

Off

 

 

 

 

 

 

 

 

 

 

 

10. Generic/baseboard heat energized

High

Off

Off

Off

Off

Off

Off

Off

Off

On

 

 

 

 

 

 

 

 

 

 

 

11. Exit(e)

Exit

 

 

 

 

 

 

 

 

 

(a)Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives.

(b)At the beginning of step 2, the controller attempts to clear all diagnostics.

(c)The low fan speed output energizes at step 3. If the unit is configured for a 1 speed fan, the fan remains on high speed at step 3.

(d)If the unit is configured for a 1- or 2-speed fan, and BOP2 is configured for an exhaust fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium speed.

(e)After step 10, the test sequence performs an exit. This initiates a reset and attempts to return the controller to normal operation.

Diagnostics

Translating Multiple Diagnostics

The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur.

Possible diagnostics include:

74

BCXC-SVX01B-EN

Page 74
Image 74
Trane BCXC-SVX01B-EN, BCVC, BCHC manual Translating Multiple Diagnostics, Tracer ZN520 test sequence