Diagnostics

Table 41. Tracer ZN010 and ZN510 controller diagnostics

Diagnostic

Latching

Fan

Valves

Electric heat

Damper

 

 

 

 

 

 

Auxiliary temperature failure

No

Enabled

No action

No action

No action

 

 

 

 

 

 

Condensate overflow detection

Yes

Off

Closed

Off

Closed

 

 

 

 

 

 

Entering water temperature

No

Enabled

Enabled

Enabled

Enabled

 

 

 

 

 

 

Fan mode failure

No

Enabled

Enabled

Enabled

Enabled

 

 

 

 

 

 

Invalid unit configuration failure

Yes

Disabled

Disabled

Disabled

Disabled

 

 

 

 

 

 

Low temperature detection

Yes

Off

Open

Off

Closed

 

 

 

 

 

 

Maintenance required

Yes

Enabled

No action

No action

No action

 

 

 

 

 

 

Setpoint

No

Enabled

No action

No action

No action

 

 

 

 

 

 

Zone temperature failure

No

Off

Closed

Off

Closed

Notes:

1.Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics affect unit operation according to priority level.

2.Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically resets when the input is present and valid.

3.Enabled: End device is allowed to run if there is a call for it to run.

4.Disabled: End device is not allowed to run even if there is a call for it to run.

5.No Action: The diagnostic has no affect on the end device.

Table 42. Tracer ZN520 diagnostics

Diagnostic

Fan

Other outputs(a)

Condensate overflow

Off

Valves closed, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Low temperature detection

Off

Valves open, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Low air flow - fan failure

Off

Valves closed, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Space temperature failure

Off

Valves closed, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Entering water temperature failure

On

Valves enabled(b), fresh air damper enabled(b), electric heat enabled(b), baseboard heat off

Discharge air temperature low limit

Off

Valves open, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Discharge air temperature failure

Off

Valves closed, fresh air damper closed, electric heat off, baseboard heat off

 

 

 

Fresh air temperature failure

On

Valves enabled, fresh air damper minimum position(c), electric heat enabled, baseboard heat

 

 

enabled

 

 

 

Relative humidity failure

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

Generic 4-20ma failure

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

CO2 input failure

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

Maintenance required

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

Local fan mode failure

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

Local setpoint failure

On

Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled

 

 

 

Invalid unit configuration

Off

Valves disabled, fresh air damper disabled, electric heat disabled, baseboard heat disabled

 

 

 

Normal - power up

On

Valves enabled, fresh air damper enabled, electric heat enabled

(a)The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.

(b)When the entering water temperature is required but not present, the Tracer™ ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When the entering water temperature sensor fails, the controller prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the Cool mode, all cooling is locked-out, but normal fan and outdoor air damper operation is permitted.

(c)When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the outdoor air temperature sensor fails or is not present, the controller prohibits economizer operation.

BCXC-SVX01B-EN

77

Page 77
Image 77
Trane BCXC-SVX01B-EN, BCVC, BCHC manual Tracer ZN010 and ZN510 controller diagnostics, Tracer ZN520 diagnostics