Controls Interface

Control Options

Blower coil air handlers are available without controls or with one of four different control options:

Control interface

Tracer™ ZN010

Tracer ZN510

Tracer ZN520

Units without controls have a junction box mounted on the drive side for motor power wire terminations. The controller is easily accessible in the control box for service. Control option descriptions follow below.

Control Interface

The control interface is for use with a field–supplied low voltage thermostat. It includes a control box with a transformer, motor contactor, and disconnect switch. All hot leads to the motor are disconnected at the contactor and disconnect switch to eliminate the risk of shock during service. The end devices are mounted with the wires pulled and terminated inside the two-sided terminal strip. All customer connections other than power are on the outside of the two-sided terminal strip.

Tracer Controllers

The Tracer™ family of controllers—ZN010, ZN510, and ZN520—offer the combined advantages of simple and dependable operation with the latest Trane-designed controller. Standard control features include options normally available on more elaborate control systems. All control options are available factory-configured or can be field-configured using Rover™ service software. For more detailed information, refer to Trane publication CNT-IOP-1, Installation, Operation, and Programming Guide (for ZN010 or ZN510), or CNT-SVX04A-EN, Installation, Operation, and Programming Guide (for ZN520).

Tracer ZN010

Tracer™ ZN010 is a stand-alone microprocessor controller.

Tracer ZN510 and ZN520

The Tracer™ ZN510 controller can be used as either a standalone or as part of a Trane Integrated Comfort™ System (ICS).

Figure 12. ZN510 control board

Figure 13. ZN520 control board

In the stand-alone configuration, ZN510 or 520 receives operation commands from the zone sensor and/or the auto changeover sensor (on auto changeover units). ZN520 also receives commands from the discharge air sensor. The entering water temperature is read from the auto changeover sensor and determines if the unit is capable of cooling or heating. The zone sensor module is capable of transmitting the following information to the controller:

Timed override on/cancel request