Installation Electrical

Table 14. Motor electrical data (continued)

Voltage

Voltage range

rpm

Rated hp

lb

FLA

LRA

 

 

 

 

 

 

 

220/50/1

198–242

1450

1/3

20.5

3.0

15.6

 

 

 

1/2

25

3.6

20.5

 

 

 

3/4

29

5.2

25.6

 

 

 

1.0

38

9.3

52.2

 

 

 

 

 

 

 

240/50/1

216–264

1450

1/3

20.5

3.3

17.1

 

 

 

1/2

25

4.0

22.7

 

 

 

3/4

29

5.5

39.1

 

 

 

1.0

38

10.6

57.8

 

 

 

 

 

 

 

190/50/3

171–209

1450

1/3

22

1.1

5.6

380/50/3

342–418

 

1/2

26

1.4

7.8

 

 

 

3/4

28

1.7

9.8

 

 

 

1.0

29

2.1

14.6

 

 

 

1.5

34

2.8

18.7

 

 

 

2.0

49

3.6

27.2

 

 

 

 

 

 

 

415/50/3

374–456

1450

1/3

22

1.2

6.8

 

 

 

1/2

26

1.5

9.4

 

 

 

3/4

28

1.9

11.0

 

 

 

1.0

29

2.5

17.4

 

 

 

1.5

34

3.1

22.6

 

 

 

2.0

49

3.6

32.3

Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs to be incorporated into the control sequence.

32

BCXC-SVX01B-EN

Page 32
Image 32
Trane BCXC-SVX01B-EN, BCVC, BCHC manual 220/50/1, 240/50/1, 190/50/3, 380/50/3, 415/50/3