Installation Electrical

Table 14. Motor electrical data

Voltage

Voltage range

rpm

Rated hp

lb

FLA

LRA

 

 

 

 

 

 

 

115/60/1

104–126

1750

1/3

18

5.8

22.8

 

 

 

1/2

21

7.2

30.4

 

 

 

3/4

29

12.0

58.4

 

 

 

1.0

29

12.8

58.4

 

 

 

 

 

 

 

Two-speed

 

 

 

 

 

 

115/60/1

104–126

1750/1160

3/4

40

8.9/6.1

42.0

 

 

 

1.0

41

11.5/8.1

58.2

 

 

 

 

 

 

 

208–230/60/1

187–253

1750

1/3

18

3.1

11.4

 

 

 

1/2

21

3.6

15.2

 

 

 

3/4

29

6.0

29.2

 

 

 

1.0

29

6.4

29.2

 

 

 

 

 

 

 

277/60/1

249–305

1750

1/3

15.5

2.5

12.1

 

 

 

1/2

21.5

3.6

19.3

 

 

 

3/4

25

4.3

25.3

 

 

 

1.0

29

5.6

32.6

 

 

 

 

 

 

 

208/60/3

187–229

1750

1/2

22

2.3

11.4

 

 

 

3/4

26

2.9

15.9

 

 

 

1.0

28

3.5

20.2

 

 

 

1.5

29

4.8

30.0

 

 

 

2.0

34

6.2

38.5

 

 

 

3.0

49

8.6

55.1

 

 

 

 

 

 

 

230/60/3

207–253

1750

1/2

22

2.4

12.8

 

 

 

3/4

26

3.0

18.6

 

 

 

1.0

28

3.6

23.0

 

 

 

1.5

29

4.8

33.4

 

 

 

2.0

34

6.2

43.6

 

 

 

3.0

49

8.6

62.0

 

 

 

 

 

 

 

460/60/3

414–506

1750

1/2

22

1.2

6.4

 

 

 

3/4

26

1.5

9.3

 

 

 

1.0

28

1.8

11.5

 

 

 

1.5

29

2.4

16.7

 

 

 

2.0

34

3.1

21.8

 

 

 

3.0

49

4.3

31.0

 

 

 

 

 

 

 

575/60/3

518–632

1750

3/4

20.5

1.1

7.5

 

 

 

1.0

22.5

1.4

9.0

 

 

 

1.5

31

1.9

13.3

 

 

 

2.0

36

2.5

17.9

 

 

 

3.0

49

3.3

23.7

Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs to be incorporated into the control sequence.

BCXC-SVX01B-EN

31

Page 31
Image 31
Trane BCHC, BCVC, BCXC-SVX01B-EN manual Motor electrical data