Start-Up

When the fan switch is in the off position, the controller does not control any unit capacity. The unit remains powered and all outputs drive to the closed position. Upon a loss of signal on the fan speed input, the controller reports a diagnostic and reverts to using the default fan speed.

On/Cancel Buttons

Momentarily pressing the on button during unoccupied mode places the controller in occupied bypass mode for 120 minutes. You can adjust the number of minutes in the unit controller configuration using Rover™ service tool. The controller remains in occupied bypass mode until the override time expires or until you press the Cancel button.

Communication Jack

Use the RJ-11 communication as the connection point from Rover™ service tool to the communication link—when the communication jack is wired to the communication link at the controller. By accessing the communication jack via Rover, you gain access to any controller on the link.

Figure 14. Resistance temperature curve for the zone sensor, entering water temperature sensor, and discharge air sensor