Maintenance

NOTICE

Belt tension!

Do not over-tension belts. Excessive belt tension will reduce fan and motor bearing life, accelerate belt wear, and could result in shaft failure.

Table 32. BCHC/BCVC fan, filter, and mixing box general data

Unit size

12

18

24

36

54

72

90

Nominal cfm

400

600

800

1200

1800

2400

3000

 

 

 

 

 

 

 

 

Air flow

 

 

 

 

 

 

 

Minimum cfm

250

375

500

750

1125

1500

1875

Maximum cfm

500

675

1000

1600

2400

3000

4000

 

 

 

 

 

 

 

 

Fan data

 

 

 

 

 

 

 

Fan wheel, in. (dia. x width)

9.5 x 4.5

9.5 x 4.5

9.5 x 9.5

9.5 x 9.5

12.6 x 9.5

12.6 x 9.5

12.6 x 9.5

Maximum rpm

2300

2300

1800

1800

1500

1500

1500

Motor hp

0.33–1.0

0.33–1.0

0.33–1.0

0.33–1.5

0.33–2.0

0.33–3.0

0.33–3.0

 

 

 

 

 

 

 

 

Unit flat filter

 

 

 

 

 

 

 

Qty. - size, in.

1 - 12 x 24 1 - 12 x 24 1 - 16 x 25 2 - 16 x 20 2 - 20 x 20 1 - 20 x 20 3 - 16 x 25

 

 

 

 

 

 

1 - 20 x 25

 

Area, sq. ft

2.000

2.000

2.778

4.444

5.556

6.250

8.333

Velocity, ft/min.

200

300

288

270

324

384

360

 

 

 

 

 

 

 

 

Angle filter

 

 

 

 

 

 

 

Qty. - size, in.

2 - 12 x 24 2 - 12 x 24 2 - 12 x 24 2 - 20 x 20 4 - 16 x 20 4 - 16 x 20 4 - 20 x 20

Area, sq. ft

4.000

4.000

4.000

5.556

8.889

8.889

11.111

Velocity, ft/min.

100

150

200

216

203

270

270

 

 

 

 

 

 

 

Bottom / top access filter box

 

 

 

 

 

 

Qty. - size, in.

1 - 12 x 20 1 - 12 x 24 1 - 16 x 25 1 - 16 x 20 1 - 16 x 20 1 - 20 x 25 2 - 16 x 25

 

 

 

 

1 - 16 x 16 1 - 20 x 20 1 - 20 x 20 1 - 14 x 25

Area, sq. ft

1.700

2.000

2.800

4.000

5.000

6.300

8.000

Velocity, ft/min.

240

300

288

300

360

384

375

 

 

 

 

 

 

 

 

Mixing box

 

 

 

 

 

 

 

Damper opening width, in.

15.5

19.5

19.5

31.5

31.5

31.5

31.5

Damper opening height, in.

7

7

7

7

12.75

12.75

12.75

Area, sq. ft

0.753

0.948

0.948

1.531

2.789

2.789

2.789

Velocity, ft/min.

531

633

844

784

645

861

1076

Note: Minimum air flow limits apply to units with hot water or electric heat only. There is no minimum airflow limit on cooling on units. Maximum airflow limits are to help prevent moisture carryover.

Table 33. BCBH/BCVC valve package waterflow limits

Tube size (in.)

gpm

 

 

1/2

8.6

 

 

3/4

19.3

 

 

1

34.3

 

 

1-1/4

53.5

 

 

BCXC-SVX01B-EN

65

Page 65
Image 65
Trane BCXC-SVX01B-EN, BCHC manual Belt tension, BCBH/BCVC valve package waterflow limits