Trane UniTrane Fan-Coil & Force Flo Air Conditioners Inverted Vertical Recessed, Model N, weights

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 21
Image 21

Installation

dimensions

& weights

 

 

 

 

Inverted Vertical Recessed, Model N

Inverted vertical recessed unit dimensions & weights, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-3 7/8

2’-8 7/8

3’-6 3/8

4’-2 7/8

5’-9 7/8

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16

5’-4 13/16

D

2 3/8

2 3/8

2 3/8

4 1/8

4 1/8

E

3’-11”

4’-3”

5’-3”

5’-5 1/2

7’-5 1/2

F

2’-6”

2’-6”

2’-6”

2’-9 1/2

2’-9 1/2

G

2’-2 1/2

2’-2 1/2

2’-2 1/2

2’-3 1/2

2’-3 1/2

H

3’-6”

4’-0”

4’-9”

5’-3”

7’-3”

operatingweight

78

88

128

139

253

shipping weight

68

78

118

129

243

Notes:

1.Coil connections are always on the side opposite the control box.

2.Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3.All duct collar dimensions are to the outside of the collar.

4.See pages 23-24 for fresh air opening dimensions.

Dimension 'D' refers to the required minimum distance between the finished floor, and the bottom of the unit.

UNT-SVX07A-EN

21

Page 21
Image 21
Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual Inverted Vertical Recessed, Model N, Installation, dimensions