mechanical
Installation requirements
Water Piping Connections to Factory- Installed Piping Package
Before installing water piping supply and return lines to factory piping package, note the following items.
•All piping connections are
•The
•The installer must provide adequate piping system filtration and water treatment.
•If the unit has a factory deluxe piping package, the piping includes a strainer with a
Note: Maintain a minimum distance of one foot between the reduction fitting for the
1.The factory piping package ships with brackets to adequately support the piping during shipment. Remove these brackets before connecting water piping to the unit.
2.Close the piping end valves to the fully open position to prevent damage to the valve seat during brazing.
3.Remove the auxiliary drain pan, if it is in place, to prevent exposure to dripping solder or excessive temperatures.
4.Solder water piping connections to supply and return end connections. Avoid overheating factory soldered joints to prevent the possibility of leakage.
5.Insulate
Condensate Drain
1.
2.Connect a
3.Slide the copper pipe over the drain pan nipple and tighten the collar on the pipe with a hose clamp (installer supplied).
Maintain a continuous drain line pitch of one inch per ten feet of drain line run to provide adequate condensate drainage. Extend the drain line straight from the drain pan a minimum distance of six inches before making any turns. The installer must provide proper support for the drain line to prevent undue stress on the auxiliary drain pan.
Install a secondary overflow drain line if necessary by punching out the overflow drain nipple on the auxiliary drain pan.
Next, place a
Note: The installer is responsible for adequately insulating field piping. See the “External Insulating Requirements section for more information.
Condensate Overflow Detection Device The condensate overflow detection device is an option on
Figure I-MR-1. Condensate float switch installed in horizontal auxilliary drain pan.
Automatic Changeover Sensor
If the unit does not have a factory piping package, the factory attaches the sensor and coiled lead wires to the piping side end panel. The installer should attach the sensor parallel to and in direct contact with the supply water pipe.
Note: The installer is responsible to ensure the changeover sensor is installed in a location that can sense active water temperature. Otherwise, the unit may fail to sense the correct operating mode and disable temperature control.
When using field supplied
Note: The maximum length of the automatic changeover wire cannot exceed ten feet from the control panel. If the sensor extends beyond the unit chassis, use shielded conductors to eliminate radio frequency interference (RFI).
Figure I-MR-2. Condensate float switch installed in vertical auxilliary drain pan.
31 |