general

Installation information

Table I-GI-1. Fan-coil component data

unit size

02

03

04

06

08

10

12

Coil Data

 

 

 

 

 

 

 

Face Area — Ft2 (cm2)

0.8 (743)

0.8 (743)

1.1 (1020)

1.6 (1490)

2.1 (1950)

3.2 (2970)

3.2 (2970)

LxDxH — In. (cm)

 

 

 

 

 

 

 

2-Row

15x1.7x8

15x1.7x8

20x1.7x8

29.5x1.7x8

38x1.7x8

57x1.7x8

57x1.7x8

 

(38x4x20)

(38x4x20)

(51x4x20)

(75x4x20)

(97x4x20)

(145x4x20)

(145x4x20)

3-Row

15x2.6x8

15x2.6x8

20x2.6x8

29.5x2.6x8

38x2.6x8

57x2.6x8

57x2.6x8

 

(38x7x20)

(38x7x20)

(51x7x20)

(75x7x20)

(97x7x20)

(145x7x20)

(145x7x20)

4-Row

15x3.5x8

15x3.5x8

20x3.5x8

29.5x3.5x8

38x3.5x8

57x3.5x8

57x3.5x8

 

(38x9x20)

(38x9x20)

(51x9x20)

(75x9x20)

(97x9x20)

(145x9x20)

(145x9x20)

Volume — Gal. (Liters)

 

 

 

 

 

 

 

1-Row(Heat)

.06 (.23)

.06 (.23)

.08 (.30)

.11 (.42)

.14 (.53)

.21 (.79)

.21 (.79)

2-Row

.12 (.45)

.12 (.45)

.15 (.57)

.22 (.83)

.28 (1.06)

.42 (1.59)

.42 (1.59)

3-Row

.18 (.68)

.18 (.68)

.23 (.87)

.33 (1.25)

.42 (1.59)

.62 (2.35)

.62 (2.35)

4-Row

.24 (.91)

.24 (.91)

.30 (1.14)

.44 (1.67)

.56 (2.12)

.83 (3.14)

.83 (3.14)

Fins/Ft (cm)

 

 

 

 

 

 

 

2-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

3-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

4-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

Reheat Coil Data (1-Row)

 

 

 

 

 

 

 

Hot Water or Steam

 

 

 

 

 

 

 

Face Area — Ft2 (cm2)

0.6

0.6

0.8

1.2

1.6

2.4

2.4

 

(557)

(557)

(743)

(1120)

(1490)

(2230)

(2230)

LxDxH — In. (cm)

15x1.5x6

15x1.5x6

20x1.5x6

29.5x1.5x6

38x1.5x6

57x1.5x6

57x1.5x6

 

(38x4x15)

(38x4x15)

(51x4x15)

(75x4x15)

(97x4x15)

(145x4x15)

(145x4x15)

Volume — Gal. (Liters)

.12 (.45)

.12 (.45)

.15 (.57)

.22 (.83)

.28 (1.06)

.42 (1.59)

.42 (1.59)

Fins/Ft (cm)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

Fan/MotorData

 

 

 

 

 

 

 

Fan Quantity

1

1

1

2

2

3

3

Size — Dia” x Width” (cm)

6.31x4

6.31x6.5

6.31x7.5

6.31x6.5

6.31x7.5

(1) 6.31x7.5

6.31x7.5

 

(16x10)

(16x17)

(16x19)

(16x17)

(16x19)

(16x19)

(16x19)

Size — Dia” x Width” (cm)

 

 

 

 

 

(2) 6.31x6.5

 

 

 

 

 

 

 

(16x6.5)

 

MotorQuantity

1

1

1

1

1

2

2

Filter Data

 

 

 

 

 

 

 

1” (cm) TA and Pl. Media

 

 

 

 

 

 

 

Quantity

1

1

1

1

1

1

1

Size — In. (cm)

87/8 x 191/8

87/8 x 191/8

87/8 x 241/8

87/8 x 335/8

87/8 x 421/8

87/8 x 611/8

87/8 x 611/8

 

(23x49)

(23x49)

(23x61)

(23x85)

(23x107)

(23x155)

(23x155)

1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)

 

 

 

Quantity

1

1

1

1

1

1

1

Size — In. (cm)

51/2 x 191/8

51/2 x 191/8

51/2 x 241/8

51/2 x 335/8

51/2 x 421/8

51/2 x 611/8

51/2 x 611/8

(14 x 49)

(14 x 49)

(14 x 61)

(14 x 85)

(14 x 107)

(14 x 156)

(14 x 156)

 

Table I-GI-2. Low vertical fan-coil component data

unit size

03

04

06

Coil Data

 

 

 

Face Area — Ft2 (cm2)

1.1 (1020)

1.6 (1490)

2.1 (1950)

LxDxH — In. (cm)

 

 

 

2-Row

20x1.7x8 (51x4x20)

29.5x1.7x8 (75x4x20)

38x1.7x8 (97x4x20)

3-Row

20x2.6x8 (51x7x20)

29.5x2.6x8 (75x7x20)

38x2.6x8 (97x7x20)

Volume — Gal. (Liters)

 

 

 

1-Row(Heat)

.08 (.30)

.11 (.42)

.14 (.53)

2-Row

.15 (.57)

.22 (.83)

.28 (1.06)

3-Row

.23 (.87)

.33 (1.25)

.42 (1.59)

Fins/Ft

 

 

 

2-Row

144 (4.7)

144 (4.7)

144 (4.7)

3-Row

144 (4.7)

144 (4.7)

144 (4.7)

Fan/MotorData

 

 

 

Fan Quantity

1

1

1

Size — Dia”x Width” (cm)

5x23 (13x59)

5x32 (13x83)

5x41 (13x105)

MotorQuantity

1

1

1

Filter Data

 

 

 

1” (2.5 cm) TA

 

 

 

Quantity

1

1

1

Size — In. (cm)

87/8x241/8 (23x61)

87/8x335/8 (23x85)

87/8 x 421/8 (23x107)

UNT-SVX07A-EN

7

Page 7
Image 7
Trane UniTrane Fan-Coil & Force Flo Air Conditioners, UNT-SVX07A-EN manual Table I-GI-1. Fan-coil component data