sequence of

Operation operation

Analog Inputs

Both Tracer ZN010 and ZN510 accept a maximum of five analog inputs. Reference Table O-SO-4.

Zone Sensors

The zone sensors available with the Tracer ZN010 and ZN510 provide up to three different inputs

1.Space temperature measurement (10KΩ thermistor)

2.Local setpoint

3.Fan mode switch

Wall mounted zone sensors include a thermistor as a component of the internal printed circuit board. Unit mounted zone sensors use a sensor placed in the unit’s return air stream.

Each zone sensor is equipped with a thumbwheel for setpoint adjustment.

Fan Mode Switch

The zone sensor may be equipped with a fan mode switch. The fan mode switch offers selections of off, low, medium, high, or auto.

Supply Fan Operation

Reference Table O-SO-5 for fan mode operation. Reference Table O-SO-5 for fan mode operation. Tracer ZN010 and ZN510 will operate in either continuous fan or fan cycling mode. The fan cycles when the fan mode switch is placed in auto. The fan runs continuous when placed in the high, medium, or low position. Use Rover, Trane’s installation and service tool, to change auto defaults.

Table O-SO-4. Analog inputs

analog input

description

application

zone

space temperature

space temperature detection

set

local setpoint

thumbwheel setpoint

fan

fan mode input

zone sensor fan switch

analog input 1 (AI1)

entering water temperature

entering water temperature detection

analog input 2 (AI2)

discharge air temperature

discharge air temperature detection

Notes:

1.The zone sensor, entering water temperature sensor, and the discharge air temperature sensor are 10KΩ thermistors. Figure 26 provides the resistance-temperature curve for these thermistors.

2.Zone sensor:

Wall mounted sensors include a thermistor soldered to the sensor’s circuit board Unit mounted sensors include a return air sensor in the unit’s return air stream.

3.Changeover units include an entering water temperature sensor.

Table O-SO-5. Fan mode operation

heating mode

 

cooling mode

 

 

 

fan mode

occupied

unoccupied

occupied

unoccupied

 

off

off

off

off

off

 

low

low

off/high (3)

low

off/high (3)

 

medium

medium

off/high (3)

medium

off/high (3)

 

high

high

off/high (3)

high

off/high (3)

 

auto

 

 

 

 

 

continuous

heat default

off/high (3)

cool default

off/high (3)

 

cycling off/heat default

off/high (3)

off/cool default

off/high (3)

 

Notes:

1.During the transition from off to any fan speed but high, Tracer ZN010 and ZN510 automatically starts the fan on high speed and runs for three seconds before transitioning to the selected speed (if it is other than high). This provides enough torque to start all fan motors from the off position.

2.When the heating output is controlled off, Tracer ZN010 and ZN510 automatically controls the fan on for an additional 30 seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.

3.Whenever two states are listed for the fan:

The first state (off) applies when there is not a call for heating or cooling. The second state (varies) applies when there is a call for heating or cooling.

The heat default is factory configured for low fan speed, and the cool default is medium.

Table O-SO-6. Valid operating range and factory default setpoints

setpoint/parameter

default setting

valid operating range

unoccupied cooling setpoint

85° F

40 to 115° F

occupied cooling setpoint

74° F

40 to 115° F

occupied heating setpoint

71° F

40 to 115° F

unoccupied heating setpoint

60° F

40 to 115° F

cooling setpoint high limit

110° F

40 to 115° F

cooling setpoint low limit

40° F

40 to 115° F

heating setpoint high limit

105° F

40 to 115° F

heating setpoint low limit

40° F

40 to 115° F

power-up control wait

0 sec

0 to 240 sec

52

UNT-SVX07A-EN

Page 52
Image 52
Trane UNT-SVX07A-EN manual Analog Inputs, Zone Sensors, Fan Mode Switch, Supply Fan Operation