Trane UniTrane Fan-Coil & Force Flo Air Conditioners Binary Inputs, Binary Outputs, sequence of

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 51
Image 51

sequence of

Operation operation

Sequence of Operation Tracer ZN010 and ZN510

Note: this section applies only to units with a Tracer ZN010 or ZN510 controller.

Power-Up Sequence

When 24 VAC power is initially applied to the Tracer ZN010 or ZN510, the following sequence occurs:

Table O-SO-1. Unit mode as related to water temperature

unit type

EWT sensor required?

coil water temperature

 

 

2-pipe changeover

yes

COOLS if: space temp - EWT

 

5°F

 

 

HEATS if: EWT - space temp

 

5°F

4-pipe changeover

yes

COOLS if: space temp - EWT

5°F

 

 

HEATS if: EWT - space temp

5°F

 

 

 

 

 

2-pipe heating only

no

hot water assumed

 

 

2-pipe cooling only

no

cold water assumed

 

 

4-pipe heat/cool

no

cold water assumed in main coil

 

 

hot water assumed in aux. coil

1.All outputs are controlled off.

2.Tracer ZN010 and ZN510 reads all input values to detemine initial values.

3.The random start time (0-25 seconds) expires.

4.Normal operation begins.

Entering Water Temperature Sampling Function

Both Tracer ZN010 and ZN510 use an entering water temperature sampling function to test for the correct water temperature for the unit operating mode. For all applications not involving changeover, the water temperature does not affect unit operation.

The entering water temperature sam- pling function opens the main hydronic valve, waits no more than three minutes to allow the water temperature to stabilize, then measures the entering water temperature to see if the correct water temperature is available.

The entering water must be five degrees or more above the space temperature to allow hydronic heating and five degrees or more below the space temperature to allow hydronic cooling.

If the correct water temperature is available, the unit begins normal heating or cooling operation. If the measured entering water temperature is too low or high, the controller closes the valve and waits 60 minutes before attempting to sample the entering water. Reference Table O-SO-1.

Binary Inputs

BIP1: Low Temperature Detection Option

The factory hard wires the low temperature detection sensor to binary input #1 (BIP1) on the Tracer ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a low temperature diagnostic when detecting low temperature. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:

fan: off

valves: open

electric heat: off

damper: closed

Note: See the “Diagnostics” section for more information.

BIP2: Condensate Overflow Detection Option

The factory hard wires the condensate overflow sensor to binary input #2 (BIP2) on the Tracer ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a condensate overflow diagnostic if condensate reaches the trip point. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:

fan: off

valves: closed

electric heat: off

BIP3: Occupancy Sensor

Binary input #3 (BIP3) on Tracer ZN010 and ZN510 is available for field- wiring an occupancy sensor, such as a binary switch or a timeclock, to detect occupancy. The sensor can be either normally open or normally closed. Reference Table O-SO-2.

Binary Outputs

Reference Table O-SO-3 for the Tracer ZN010 and ZN510’s six binary outputs.

Table O-SO-3. Binary outputs

binary output

description

pin

BOP1

fan high speed

J1-1

BOP2

fan medium speed

J1-2

BOP3

fan low speed

J1-4

BOP4

main valve

J1-5

BOP5

auxiliary valve/electric heat

J1-6

BOP6

2-position fresh air damper

J1-7

Notes:

1.In a four-pipe application, BOP4 is used for cooling and BOP5 is used for heating.

2.If no valves are ordered with the unit, the factory default for the Tracer ZN010 and ZN510 controller are:

BOP4 configured as normally closed BOP5 configured as normally open

3.If the fresh air damper option is not ordered on the unit, BOP6 will be configured as none.

Table O-SO-2. Occupancy sensor state table

sensor type

sensor position

unit occupancy mode

normally open

open

occupied

normally open

closed

unoccupied

normally closed

open

unoccupied

normally closed

closed

occupied

UNT-SVX07A-EN

51

Page 51
Image 51
Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual Binary Inputs, Binary Outputs, sequence of, Operation operation