Trane UniTrane Fan-Coil & Force Flo Air Conditioners, UNT-SVX07A-EN manual Maintenance diagnostics

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 63
Image 63

Maintenance diagnostics

Table M-D-6. Electric Heat Not Operating

Probable Cause

Explanation

Normal operation

The controller cycles electric heat on and off to meet the unit capacity requirements.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the controller,

 

the units shuts off the electric heat.

Communicated disable

Numerous communicated requests may disable electric heat, including an auxiliary heat enable input and the heat/cool mode input.

 

Depending on the state of the communicated request, the unit may disable electric heat.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on the current step in the test sequence, the electric heat may not be on. Refer to the “Manual Output Test”

 

section.

Diagnostic present

A specific list of diagnostics affects electric heat operation. For more information, see the “Diagnostics” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does

 

not match the actual end device, the electric heat may not work properly.

No power to the controller

If the controller does not have power, electric heat does not operate. For the controller to operate normally, a

 

24VAC input voltage must be applied. Whenthe green LED is off continuously, the controller does not have sufficient power or has

 

failed.

Unit Wiring

The wiring between the controller outputs and the electric heat contacts must be present and correct for normal electric heat

 

operation. Refer to the typicalunit wiring diagrams in the Appendix of this manual.

Table M-D-7. Fresh Air Damper Stays Open

Probable Cause

Explanation

Normal operation

The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status. Normally, the

 

fresh air damper is open during moccupied mode when the fan is running and closed during unoccupied mode.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to

 

the “Manual Output Test” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit

 

configuration does not match the actualend device, the damper may not work correctly.

Unit wiring

The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer

 

to the typical unit wiringdiagrams in the Appendix of this manual.

Table M-D-8. Fresh Air Damper Stays Closed

Probable Cause

Explanation

Normal operation

The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status. Normally, the

 

fresh air damper is open during moccupied mode when the fan is running and closed during unoccupied mode.

Warmup and cooldown

The controller includes both a warmup and cooldown sequence to keep the fresh air damper closed during the transition from

 

unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the

 

controller, the unit closes the fresh air damper.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to

 

the “Manual Output Test” section.

Diagnostic present

A specific list of diagnostics effects fresh air damper operation. For more information, see the “Diagnostics” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit

 

configuration does not match the actualend device, the damper may not work correctly.

No power to the controller

If the controller does not have power, the fresh air damper does not operate. For the controller to operate normally, a

 

24 VAC input voltage must be applied.When the green LED is off continuously, the controller does not have sufficient power or has

 

failed.

Unit wiring

The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer

 

to the typical unit wiringdiagrams in the Appendix of this manual.

UNT-SVX07A-EN

63

Page 63
Image 63
Trane UniTrane Fan-Coil & Force Flo Air Conditioners Maintenance diagnostics, Table M-D-6. Electric Heat Not Operating