Trane UNT-SVX07A-EN manual sequence of, Operation operation, Table O-SO-14. Analog inputs

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 58
Image 58

sequence of

Operation operation

Table O-SO-14. Analog inputs

description

terminals

function

range

zone

TB3-1

space temperature input

5° to 122°F (-15° to 50°C)

ground

TB3-2

analog ground

NA

set

TB3-3

setpoint input

40° to 115°F (4.4° to 46.1°C)

fan

B3-4

fan switch input

4821 to 4919 W (off)

 

 

 

2297 to 2342 W (auto)

 

 

 

10593 to 10807 W (low)

 

 

 

13177 to 13443 W (medium)

 

 

 

15137 to 16463 W (high)

ground

TB3-6

analog ground

NA

analog input 1

J3-1

entering water temperature

-40° to 212°F (-40° to 100°C)

 

J3-2

analog ground

NA

analog input 2

J3-3

discharge air temperature

-40° to 212°F (-40° to 100°C)

 

J3-4

Analog ground

NA

analog input 3

J3-5

fresh air temp/generic temp

-40° to 212°F (-40° to 100°C)

 

J3-6

Analog ground

NA

analog input 4

J3-7

universal input

0 – 100%

 

 

generic 4-20ma

0 – 100%

 

 

humidity

0 – 2000ppm

 

 

CO2

 

 

J3-8

analog ground

NA

ground

J3-9

analog ground

NA

Notes:

1.The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10Kthermistors.

2.Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board. Unit mounted sensors include a return air sensor in the units return air stream.

3.Changeover units include an entering water temperature sensor.

Table O-SO-15. Analog inputs

description

terminals

function

range

zone

TB3-1

space temperature input

5° to 122°F (-15° to 50°C)

ground

TB3-2

analog ground

NA

set

TB3-3

setpoint input

40° to 115°F (4.4° to 46.1°C)

fan

B3-4

fan switch input

4821 to 4919 W (off)

 

 

 

2297 to 2342 W (auto)

 

 

 

10593 to 10807 W (low)

 

 

 

13177 to 13443 W (medium)

 

 

 

15137 to 16463 W (high)

ground

TB3-6

analog ground

NA

analog input 1

J3-1

entering water temperature

-40° to 212°F (-40° to 100°C)

 

J3-2

analog ground

NA

analog input 2

J3-3

discharge air temperature

-40° to 212°F (-40° to 100°C)

 

J3-4

Analog ground

NA

analog input 3

J3-5

fresh air temp/generic temp

-40° to 212°F (-40° to 100°C)

 

J3-6

Analog ground

NA

analog input 4

J3-7

universal input

0 – 100%

 

 

generic 4-20ma

0 – 100%

 

 

humidity

0 – 2000ppm

 

 

CO2

 

 

J3-8

analog ground

NA

ground

J3-9

analog ground

NA

Notes:

1.The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10KW thermistors.

2.Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board. Unit mounted sensors include a return air sensor in the units return air stream.

3.Changeover units include an entering water temperature sensor.