Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual Fan Mode Operation, sequence of

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 55
Image 55

sequence of

Operation operation

Fan Mode Operation

For multiple fan speed applications, the TracerZN520 controller offers additional fan configuration flexibility. Separate default fan speeds for heating and cooling modes can be configured. The fan runs continuously for requested speeds (off, high, medium, or low). When the fan mode switch is in the Auto position or a hardwired fan mode input does not exist, the fan operates at the default configured speed. See Table 21 for default fan configuration for heat and cool mode. During unoccupied mode, the fan cycles between high speed and off with heating and cooling fan modes. If the requested speed is off, the fan always remains off.

During dehumidification, when the fan is on Auto, the fan speed can switch depending on the error. Fan speed increases as the space temperature rises above the active cooling setpoint.

Additional flexibility built into the control- ler allows you to enable or disable the local fan switch input. The fan mode request can be either hardwired or communicated to the controller. When both are present, the communicated request has priority over the hardwired input. See Tables 22, 23, and 24.

Table O-SO-7. Fan configuration

 

auto fan

fan speed

 

operation

default

Heating

continuous

off

 

 

low

 

 

medium

 

 

high

Cooling

continuous

off

 

 

low

 

 

medium

 

 

high

Table O-SO-8. Local fan switch enabled

Communicated

Fan switch (local)

Fan operation

fan speed input

 

 

Off

Ignored

Off

Low

Ignored

Low

Medium

Ignored

Medium

High

Ignored

High

Auto

Off

 

Low

 

 

Medium

 

 

High

 

 

Auto

Off

 

Low

 

 

Medium

High

Auto (configured default, determined by heat/cool mode)

Table O-SO-9. Fan operation in heating and cooling modes

 

Heating

Cooling

Fan mode

Occ.

Unocc.

Occ.

Unocc.

off

off

off

off

off

Low

low

off/high

low

off/high

Medium

med

off/high

med

off/high

High

high

off/high

high

off/high

Auto

default

off/high

default

off/high

 

fan sp.

 

fan sp.

 

Table O-SO-10. Local fan switch disabled or not present

Communicated fan speed input

Fan operation

Off

Off

Low

Low

Medium

Medium

High

High

Auto (or not present)

Auto (fan runs at

 

the default speed

Continuous Fan Operation

During occupied and occupied standby modes, the fan normally is on. For multiple speed fan applications, the fan normally operates at the selected or default speed (off, high, medium, or low). When fan mode is auto, the fan operates at the default fan speed.

During unoccupied mode, the controller controls the fan off. While unoccupied, the controller heats and cools to maintain the unoccupied heating and cooling setpoints. In unoccupied mode, the fan is controlled on high speed only with heating or cooling.

The unit fan is always off during occupied, occupied standby, and unoccupied modes when the unit is off due to a diagnostic or when the unit is in the off mode due to the local zone sensor module, a communi- cated request, or the default fan speed (off).

If both a zone sensor module and communicated request exist, the commu- nicated request has priority.

Fan Cycling Operation

TracerZN520 does not support fan cycling in occupied mode. The fan cycles between high speed and off in the unoccupied mode only. The controller’s cascade control algorithm requires continuous fan operation in the occupied mode.

Fan Off Delay

When a heating output is controlled off, the Tracer ZN520 controller automatically holds the fan on for an additional 30 seconds. This 30-second delay gives the fan time to blow off any residual heat from the heating source, such as a steam coil. When the unit is heating, the fan off delay is normally applied to control the fan; otherwise, the fan off delay does not apply.

Table O-SO-11. Relationship between outdoor temperature sensors and damper position

Outdoor Air Temp.

Modulating Outdoor Air Damper

 

 

 

 

occupied or occupied bypass

occupied standby

unoccupied

none or invalid

open to occupied minimum position

open to occupied standby minimum position

closed

failed

open to occupied minimum position

open to occuied standby minimum position

closed

present and economizing feasible

economizing minimum postion to 100%

economizing between occupied standby

open & economizing when

 

 

 

minimum position to 100%

unit is operating, closed

 

 

 

 

otherwise

present & economizing not feasible

open to occupied minimum position

open to occupied standby minimum position

closed

UNT-SVX07A-EN

55

Page 55