Trane UniTrane Fan-Coil & Force Flo Air Conditioners Maintenance diagnostics, Manual Output Test

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 61
Image 61

Maintenance diagnostics

Translating Multiple Diagnostics

The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur.

Possible diagnostics include:

Low temperature detection

Condensate overflow

Low air flow - fan status

Discharge air temp limit

Space temperature failure1

Entering water temp failure1

Discharge air temp failure1

Outdoor air temp failure1

Local setpoint failure1

Local fan mode failure1

CO2 sensor failure1

Generic AIP failure1

Humidity input failure1

Defrosting compressor lockout1

Maintenance required

Invalid unit configuration

Generic temperature failure

Discharge air low limit

Table M-D-2. Tracer ZN510 controller diagnostics

diagnostic

latching?

fan

valves

elec heat

damper

auxiliary

no

enabled

no action

no action

no action

temp. failure

 

 

 

 

 

condensate

yes

off

closed

off

closed

overflow

 

 

 

 

 

detection

 

 

 

 

 

entering

no

enabled

enabled

enabled

enabled

water temp.

 

 

 

 

 

failure

 

 

 

 

 

fan mode

no

enabled

enabled

enabled

enabled

failure

 

 

 

 

 

invalid unit

yes

disabled

disabled

disabled

disabled

configuration

 

 

 

 

 

failure

 

 

 

 

 

low temp.

yes

off

open

off

closed

detection

 

 

 

 

 

maintenance

yes

enabled

no action

no action

no action

required

 

 

 

 

 

setpoint

no

enabled

no action

no action

no action

zone temp. failure

no

off

closed

off

closed

Notes:

Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics affect unit operation according to priority level.

Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically resets when the input is present and valid.

Enabled: End device is allowed to run if there is a call for it to run.

Disabled: End device is not allowed to run even if there is a call for it to run.

No Action: The diagnostic has no affect on the end device.

1Non-latching diagnostics automatically reset when the input is present and valid.

Resetting Diagnostics

There are a number of ways in which diagnostics are reset:

1.Automatic reset by the controller

2.By initiating a manual output test at the controller

3.By cycling power to the controller

4.Through Rover™, Trane’s service tool

5.Tracer ZN520: by using any other communicating device ab le to access the controller’s diagnostic reset input.

6.Tracer ZN520: by cycling the fan switch from Off to any speed setting.

Automatic Reset by the Controller The controller includes an automatic diagnostic reset function that attempts to automatically restore the unit when a low temperature diagnostic occurs.

Note: The controller implements the automatic diagnostic reset function only once every 24 hours. For the controller to increment the 24 hour timer, you must maintain power to the controller. Cycling power resets all timers and counters.

After the controller detects the first special diagnostic, the unit waits 30 minutes before invoking the automatic diagnostic reset function. The automatic diagnostic reset function clears the special diagnostic and attempts to restore the controller to normal operation. The controller resumes normal operation until another diagnostic occurs.

Note: The automatic diagnostic reset function does not operate during the manual output test sequence.

If a special diagnostic occurs within 24 hours after an automatic diagnostic reset, the controller must be manually reset. Other possible methods of resetting diagnostics are described in the sections that follow.

Manual Output Test

To verify proper end device operation, press the controller’s Test button. This exercise will verify all outputs in a predefined sequence, the first of which will attempt to reset the controller diagnostics if any are present.

Cycling Power to the Controller After removing and reapplying the 24 VAC power from the board, the unit cycles through a power-up sequence. By default, the controller attempts to reset all diagnostics present at power-up. Diagnostics present at power-up and those that occur after power-up are handled according to Table M-D-2.

Using Trane’s Service Tool, Rover™ Rover™, Trane’s service tool, can reset diagnostics present in the controller and troubleshoot the unit. For more information, refer to the Trane publication EMTX-SVX01D-EN,Rover Installation, Operation and Programming Guide.

Diagnostic Reset

Any device that can communicate the network variable nviRequest (enumeration “clear_alarm”) can reset diagnostics in the Tracer ZN520 controller.The controller also attempts to reset diagnostics whenever power is cycled.

Cycling the Fan Switch

Cycle the fan speed switch from Off to any speed and the controller resets all diagnostics. Diagnostics may recur immediately if the problem still exists.

UNT-SVX07A-EN

61