pre-installation

Installation considerations

Service Access

Service access is available from the front on vertical units and from the bottom on horizontal units. Cabinet and recessed units have removable front or bottom panels to allow access into the unit. See Figure I-PC-1 for recommended service and operating clearances.

Units have either right or left hand piping. Reference piping locations by facing the front of the unit (airflow discharges from the front). The control panel is always on the end opposite the piping.

The fan board assembly and main drain pan are easily removable for cleaning. See the“Maintenance” section for more details on servicing.

Pre-Installation Checklist

Complete the following checklist before beginning unit installation.

! Verify the unit size and tagging with the

unit nameplate.

! Make certain the floor or foundation is

level, solid, and sufficient to support the

unit and accessory weights. See the

Dimensions and Weights section. Level

or repair the floor before positioning the

unit if necessary.

!Allow minimum recommended

clearances for routine maintenance and

24"

model B, vertical cabinet model L, low vertical cabinet

12" both sides

model D, horizontal cabinet

12" both sides

3"

model A, vertical concealed model K, low vertical concealed model H, vertical recessed

8.5" both sides

24"

front discharge

28"

model C, horizontal concealed model E, horizontal recessed

8.5" both sides

36"

28"

service. Refer to unit submittals for

dimensions.

! Allow one and one half fan diameters

above the unit before the discharge

ductwork makes any turns.

Figure I-PC-1. Recommended service clearances

UNT-SVX07A-EN

29

Page 29
Image 29