Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual electrical, Installation requirements

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 39
Image 39

electrical

Installation requirements

Table I-ER-10. Force Flo single-stage, max kW electric heat

unit

 

 

 

 

heater

heater

size

volts

hz

phase

wires

kW

amps/ph

 

208

 

1

2

2.25

10.9

 

240

 

1

2

3.0

12.5

02

277

60

1

2

3.0

10.9

 

208

 

3

3

2.25

6.3

 

240

 

3

3

3.0

7.3

 

480

 

3

4

3.0

3.7

 

208

 

1

2

4.5

21.7

 

240

 

1

2

6.0

25.0

03

277

60

1

2

6.0

21.7

 

208

 

3

3

4.5

12.6

 

240

 

3

3

6.0

14.5

 

480

 

3

4

6.0

7.3

 

208

 

1

2

5.7

27.5

 

240

 

1

2

7.5

31.3

04

277

60

1

2

7.5

27.1

 

208

 

3

3

5.7

15.9

 

240

 

3

3

7.5

18.1

 

480

 

3

4

7.5

9.1

 

208

 

1

2

7.9

38.0

 

240

 

1

2

10.5

43.8

06

277

60

1

2

10.5

38.0

 

208

 

3

3

7.9

21.9

 

240

 

3

3

10.5

25.3

 

480

 

3

4

10.5

12.7

Note: All data based on individual units. Electric heat will operate only with fan at high speed.

Table I-ER-11. Force Flo single stage, low kW electric heat

unit size

voltage

# wires

kW

amps/ph

kW

amps/ph

kW

amps/ph

02

208/60/1

2

0.75

3.7

1.5

7.3

 

 

 

240/60/1

2

1.0

4.2

2.0

8.4

 

 

 

277/60/1

2

1.0

3.7

2.0

7.3

 

 

03

208/60/1

2

2.25

10.9

 

 

 

 

 

240/60/1

2

3.0

12.5

 

 

 

 

 

277/60/1

2

3.0

10.9

 

 

 

 

 

208/60/3

3

2.25

6.3

 

 

 

 

 

240/60/3

3

3.0

7.3

 

 

 

 

 

480/60/3

4

3.0

3.7

 

 

 

 

04

208/60/1

2

2.25

10.9

 

 

 

 

 

240/60/1

2

3.0

12.5

 

 

 

 

 

277/60/1

2

3.0

10.9

 

 

 

 

 

208/60/3

3

2.25

6.3

 

 

 

 

 

240/60/3

3

3.0

7.3

 

 

 

 

 

480/60/3

4

3.0

3.7

 

 

 

 

06

208/60/1

2

2.25

10.9

3.3

15.9

 

 

 

240/60/1

2

3.0

12.5

4.5

18.8

 

 

 

277/60/1

2

3.0

10.9

4.5

16.3

 

 

 

208/60/3

3

2.25

6.3

3.3

9.2

 

 

 

240/60/3

3

3.0

7.3

4.5

10.9

 

 

 

480/60/3

4

3.0

3.7

4.5

5.5

 

 

08

208/60/1

2

2.25

10.9

3.3

15.9

4.5

21.7

 

240/60/1

2

3.0

12.5

4.5

18.8

6.0

25.0

 

277/60/1

2

3.0

10.9

4.5

16.3

6.0

21.7

 

208/60/3

3

2.25

6.3

3.3

9.2

4.5

12.5

 

240/60/3

3

3.0

7.3

4.5

10.9

6.0

14.5

 

480/60/3

4

3.0

3.7

4.5

5.5

6.0

7.3

10

208/60/1

2

2.25

10.9

3.3

15.9

5.7

27.5

 

240/60/1

2

3.0

12.5

4.5

18.8

7.5

31.3

 

277/60/1

2

3.0

10.9

4.5

16.3

7.5

27.1

 

208/60/3

3

2.25

6.3

3.3

9.2

5.7

15.9

 

240/60/3

3

3.0

7.3

4.5

10.9

7.5

18.1

 

480/60/3

4

3.0

3.7

4.5

5.5

7.5

9.1

12

208/60/1

2

2.25

10.9

3.3

15.9

6.6

31.8

 

240/60/1

2

3.0

12.5

4.5

18.8

9.0

37.5

 

277/60/1

2

3.0

10.9

4.5

16.3

9.0

32.5

 

208/60/3

3

2.25

6.3

3.3

9.2

6.6

18.4

 

240/60/3

3

3.0

7.3

4.5

10.9

9.0

21.7

 

480/60/3

4

3.0

3.7

4.5

5.5

9.0

10.9

Note: All data based on individual units. Electric heat will operate only with fan at high speed.

UNT-SVX07A-EN

39

Page 39
Image 39
Trane UniTrane Fan-Coil & Force Flo Air Conditioners, UNT-SVX07A-EN manual electrical, Installation requirements