Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual electrical, Installation requirements

Models: UniTrane Fan-Coil & Force Flo Air Conditioners UNT-SVX07A-EN

1 80
Download 80 pages 42.33 Kb
Page 37
Image 37

electrical

Installation requirements

Table I-ER-2. Low vertical free discharge motors, 115 volt

size

FLA

HP (kW)

 

RPM

03

0.7

.03 (0)

H

1090

 

 

 

M

770

 

 

 

L

560

04

0.8

.03 (0)

H

1090

 

 

 

M

750

 

 

 

L

560

06

1.1

.03 (0)

H

1115

 

 

 

M

760

 

 

 

L

560

Note:

Actual rpm will vary with application and configuration.

Table I-ER-3. Decimal to fractional HP (kW) conversion

FC

Decimal

Fraction

02

 

.03

1/30

 

 

.07

1/15

03

 

.04

1/25

 

 

.05

1/20

 

 

.08

1/12

04

 

.05

1/20

 

 

.06

1/16

 

 

.10

1/10

 

 

.13

 

1/8

06

 

.07

1/15

 

 

.12

 

1/8

 

 

.16

 

1/6

 

 

.24

 

1/4

08

 

.12

 

1/8

 

 

.13

 

1/8

 

 

.24

 

1/4

10

.05

.07

1/20

1/15

 

.06

.12

1/16

1/8

 

.10

.16

1/10

1/6

 

.13

.24

1/8

1/4

12

.05

.12

1/20

1/8

 

.06

.13

1/16

1/8

 

.10

.24

1/10

1/4

 

.13

.24

1/8

1/4

low vertical

 

.03

1/30

03, 04, 06

 

 

 

 

Note:

Values for fractional HP’s (kW’s) are approximate values and not necessarily the actual HP (kW).

Table I-ER-4. Free discharge motors on units with two-row, electric, or steam coils

unit

 

115 volt

 

208-230 volt

 

277-480 volt

 

rpm

 

size

FLA

hp (kW)

FLA

hp (kW)

FLA

hp (kW)

H

M

L

02

0.6

.03 (.02)

0.3

.03 (.02)

0.2

.03 (.02)

980

840

655

03

0.7

.04 (.02)

0.4

.04 (.02)

0.3

.04 (.02)

980

780

580

04

0.9

.05 (.04)

0.5

.05 (.04)

0.4

.05 (.04)

1050

780

580

06

1.2

.07 (.05)

0.6

.07 (.05)

0.5

.07 (.05)

1030

780

580

08

1.4

.12 (.09)

0.9

.12 (.09)

0.6

.12 (.09)

1080

800

600

10

0.9

.05 (.04)

0.5

.05 (.04)

0.4

.05 (.04)

1050

780

580

 

1.2

.07 (.05)

0.6

.07 (.05)

0.5

.07 (.05)

1030

780

580

12

0.9

.05 (.04)

0.5

.05 (.04)

0.4

.05 (.04)

1050

780

580

 

1.4

.12 (.09)

0.9

.12 (.09)

0.6

.12 (.09)

108

800

600

Table I-ER-5. High static motors on units with two-row, electric, or steam coils

unit

 

115 volt

 

208-230 volt

 

277- 480 volt

 

rpm

 

size

FLA

hp (kW)

FLA

hp (kW)

FLA

hp (kW)

H

M

L

02

1.1

.07 (.05)

0.6

.07 (.05)

0.5

.07 (.05)

1480

1110

865

03

1.4

.08 (.06)

0.7

.08 (.06)

0.6

.08 (.06)

1400

1175

860

04

1.6

.10 (.07)

0.8

.10 (.07)

0.7

.10 (.07)

1475

1315

1070

06

2.6

.16 (.12)

1.2

.16 (.12)

1.0

.16 (.12)

1400

1070

855

08

3.4

.24 (.18)

1.4

.24 (.18)

1.1

.24 (.18)

1475

1285

975

10

1.6

.10 (.07)

0.8

.10 (.07)

0.7

.10 (.07)

1475

1315

1070

 

2.6

.16 (.12)

1.2

.16 (.12)

1.0

.16 (.12)

1400

1070

855

12

1.6

.10 (.07)

0.5

.10 (.07)

0.7

.10 (.12)

1475

1315

1240

 

3.4

.24 (.18)

0.9

.24 (.18)

1.1

.24 (.18)

1475

1285

975

Table I-ER-6. Free discharge motors on units with three and four-row coils

unit

 

115 volt

 

208-230 volt

277-480 volt

 

rpm

 

size

FLA

hp(kW)

FLA

hpP(kW)

FLA

hp (kW)

H

M

L

02

0.6

.03 (.02)

0.3

.03 (.02)

0.2

.03 (.02)

980

840

655

03

0.8

.05 (.04)

0.5

.05 (.04)

0.4

.05 (.04)

1080

800

600

04

1.0

.06 (.04)

0.6

.06 (.04)

0.5

.06 (.04)

1080

800

600

06

1.4

.12 (.09)

0.9

.12 (.09)

0.6

.12 (.09)

1080

800

600

08

1.7

.13 (.10)

1.0

.13 (.10)

0.8

.13 (.10)

1080

800

600

10

1.0

.06 (.04)

0.6

.06 (.04)

0.5

.06 (.04)

1080

800

600

 

1.4

.12 (.09)

0.9

.12 (.09)

0.6

.12 (.09)

1080

800

600

12

1.0

.06 (.04)

0.6

.06 (.04)

0.5

.06 (.04)

1080

800

600

 

1.7

.13 (.10)

1.0

.13 (.10)

0.8

.13 (.10)

1080

800

600

Table I-ER-7. High static motors on units with three and four-row coils

unit

 

115 volt

 

208-230 volt

 

277-480 volt

 

rpm

 

size

FLA

hp (kW)

FLA

hp (kW)

FLA

hp (kW)

H

M

L

02

1.1

.07 (.05)

0.6

.07 (.05)

0.5

.07 (.05)

1480

1110

865

03

1.3

.08 (.06)

0.7

.08 (.06)

0.5

.08 (.06)

1500

1355

1110

04

2.1

.13 (.10)

0.9

.13 (.10)

0.7

.13 (.10)

1580

1375

1240

06

3.4

.24 (.18)

1.4

.24 (.18)

1.1

.24 (.18)

1475

1285

975

08

3.4

.24 (.18)

1.4

.24 (.18)

1.1

.24 (.18)

1475

1285

975

10

2.1

.13 (.10)

0.9

.13 (.10)

0.7

.13 (.10)

1580

1375

1240

 

3.4

.24 (.18)

1.4

.24 (.18)

1.1

.24 (.18)

1475

1285

975

12

2.1

.13 (.10)

0.9

.13 (.10)

0.7

.13 (.10 )

1580

1375

1240

 

3.4

.24 (.18)

1.4

.24 (.18)

1.1

.24 (.18)

1475

1285

975

Note: Actual rpm will vary with application and configuration. Size 10 & 12 units have two motors.

UNT-SVX07A-EN

37

Page 37
Image 37
Trane UniTrane Fan-Coil & Force Flo Air Conditioners, UNT-SVX07A-EN manual electrical, Installation requirements