8 – Start-Up, Shutdown and Bypass

1

8-1 Control Panel and Breaker Diagrams

 

 

 

 

 

2

 

A

“NORMAL” LED

 

 

“BATTERY” LED

 

B

 

 

 

“BYPASS” LED

 

 

 

C

 

 

 

 

“FAULT” LED

 

 

 

D

 

 

 

 

LCD Status Screen

3

 

E

 

 

 

 

F

“ESC” (Escape) Button

 

 

 

Scroll Buttons (

and )

 

 

G

 

 

 

Enter Button (

)

4

 

H

 

 

ON Button

 

 

I

 

 

 

 

OFF Button

 

 

 

J

 

 

 

 

“EPO” (Emergency Power Off) Button

 

 

K

5

 

 

Output Circuit Breaker Switch

 

L

 

 

 

 

M

Manual Bypass Circuit Breaker Switch

 

 

 

Bypass Input Circuit Breaker Switch

 

 

N

 

 

 

Main Input Circuit Breaker Switch

6

 

O

 

 

 

 

E

F

I

K

A

 

 

 

B

G

 

 

C

 

 

 

 

 

D

 

 

 

 

H

J

 

Control Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

O

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

Input

 

 

 

O

N

M

L

Front Panel

 

Back Panel

 

Circuit Breaker Switches

8-2 Preliminary Checklist (Single UPS)

• All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).

7 • Confirm that no voltage potential exists between Neutral and Ground.

• Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.

Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS system will provide AC power to the connected equipment load.

8

8-3 Normal Start-Up Procedure (Single UPS)

9

10

11

12

13

1 If there is an external battery cabinet connected, switch on the circuit breaker A of the external battery cabinet.

2 Confirm that the manual bypass circuit breaker switch A is off.

A

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

O

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

Input

 

 

A

2 Front Panel

Back Panel

20