11 – Especificaciones

1

11-1 Especificaciones Técnicas del Sistema UPS

 

Modelo (Capacidad)

SU80K (80kVA/64kW)

Entrada

Voltaje de Entrada

 

120/208V CA, 3Ø, 4 hilos + tierra, wye

 

 

 

 

 

Regulación de Voltaje

 

-25% ~ +20%

 

Distorsión Armónica

 

< 5% (Carga Llena/Plena Carga)

 

 

 

 

 

PFC (Carga Llena/Plena Carga)

 

> 0.99

 

 

 

 

 

Frecuencia

 

50 / 60 Hz

 

Tolerancia de Frecuencia

 

45 ~ 65 Hz

 

 

 

 

Salida

Voltaje de Salida

 

120/208V CA, 3Ø, 4 hilos + tierra, wye

 

 

 

 

 

Frecuencia de Salida

 

50 / 60 Hz

 

 

 

 

 

Armónica Total (Carga lineal)

 

<3%

 

 

 

 

 

Regulación de voltaje

Estático

±1%

 

 

 

 

 

 

Dinámico

±7% (10% ~ 90% Carga Lineal)

 

 

 

 

 

Regulación de

Oscilador Interior

±0.05 Hz

 

Frecuencia

 

 

 

Sincronizado

±5%

 

 

 

 

 

 

 

Sobrecarga

 

<125% : 10 minutos; <150% : 1 minuto

 

 

 

 

Advertencia

Respaldo de Batería

 

Intermitente

Audible

 

 

 

Mensajes de Errores

 

En Forma Continua

 

 

 

 

 

 

Display/

LED

 

Estado del UPS: Normal • Derivación Respaldo • Falla

Visualización

 

 

 

LCD

 

Entrada/Salida • Derivación Inversor • Frecuencia • Carga • Voltaje de la

 

 

 

 

 

Batería • Mensajes anormales del UPS con auto diagnostico inteligente.

 

 

 

 

Interfaz

Estándar

 

RS-232, Contacto Seco

 

 

 

 

 

Opcional

 

SNMPWEBCARD

 

 

 

 

Otros

Redundancia en Paralelo

 

Sí (1+1 para 2 sistemas UPS del mismo tipo y capacidad únicamente.)

 

 

 

 

 

EPO

 

Estándar (Local y Remoto)

 

 

 

 

 

SRAM de Registro de Eventos

 

500 Registros

 

 

 

 

 

Parámetro de configuración

 

 

 

 

 

 

Instalación Hot Standby

 

Opcional

 

 

 

 

Compensación de la Temperatura de la Batería

Opcional

 

 

 

 

 

Arranque en Frío con la Batería

 

Estándar

 

 

 

 

En Conjunto

Eficiencia

Normal

92%

 

 

 

 

 

 

ECO

96%

 

 

 

 

 

Tiempo de Transferencia

 

0 ms

 

 

 

 

 

Temperatura

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

Humedad (sin condensación)

 

90%

 

 

 

 

 

Ruido (1 m)

 

70 dBA

 

Dimensiones (Módulo de Potencia)

Ancho

520 mm

 

 

Fondo

1026 mm

 

 

Alto

1696 mm

 

 

 

 

 

Peso (Módulo de Potencia)

 

655 kg

 

 

 

 

2

3

4

5

6

7

8

9

10

11

11-2 Tabla de Resistencia/Carga del Piso del Sistema UPS

Modelo

SU80K

Peso

655 kg

 

 

Carga/Resistencia

1228 kg/m2

 

 

12

11-3 Tabla de Resistencia/Carga del Piso de los Módulos de Baterías

 

BP480V26B

BP480V40C

13

 

(40 Baterías de 12V;

(40 Baterías de 12V;

Modelo

26AH cada uno)

40AH cada una)

 

Peso

470 kg

700 kg

 

 

 

 

 

Carga/Resistencia

1064 kg/m2

1575 kg/m2

 

 

 

 

 

93

200803004 93-2793 SU80k manual 4C.indd S93

6/16/2008 1:44:52 PM

Page 93
Image 93
Tripp Lite SU80K Especificaciones Técnicas del Sistema UPS, Tabla de Resistencia/Carga del Piso del Sistema UPS

SU80K specifications

The Tripp Lite SU80K is a robust and reliable uninterruptible power supply (UPS) solution, designed to provide essential backup power to critical equipment in various environments such as data centers, telecommunications, and industrial settings. This high-capacity UPS offers 80 kVA of power, ensuring optimal protection for vital systems against power interruptions and fluctuations.

One of the main features of the SU80K is its advanced double-conversion technology, which provides clean and consistent power by converting incoming AC power to DC and then back to AC. This process not only isolates connected equipment from raw utility power, but it also ensures that sensitive electronic devices maintain a steady voltage and frequency, ultimately enhancing their performance and lifespan.

In terms of efficiency, the SU80K is equipped with an energy-efficient design that maximizes operation while minimizing energy consumption. The unit operates with an efficiency rating of up to 97% in online mode, which contributes to reduced operational costs over time and is especially beneficial for large-scale deployments.

Another notable characteristic of the SU80K is its modular design, which allows for flexibility and scalability. Users can add additional battery packs to extend runtime, enabling the UPS to adapt to changing power needs without requiring complete system replacement. This feature is particularly advantageous for growing businesses that need to expand their backup power capabilities progressively.

The SU80K also includes advanced monitoring and management options, with an optional network management card that enables remote monitoring via a web interface. This capability provides real-time data on the UPS’s status, battery health, and load levels, allowing IT administrators to make informed decisions to maintain system availability.

Additionally, the UPS features multiple communication ports, including RS-232 and USB interfaces, ensuring compatibility with various devices and ease of integration into existing systems. It also supports SNMP protocols, allowing for seamless integration with network management systems.

Overall, the Tripp Lite SU80K combines high performance, advanced features, and user-friendly management options to create an ideal solution for businesses that require reliable and efficient power protection for their critical equipment. With its strong build quality and commitment to performance, the SU80K stands out as a versatile choice for ensuring business continuity in the face of power disturbances.