7 – Operating Modes (continued)

1

7-5 Online Mode (Parallel UPS)

Parallel redundancy (1+1) provides UPS system redundancy or

2 increased total capacity. Under parallel redundancy, the total load is shared by two UPS systems. If one of the UPS systems malfunctions, the total connected equipment load is supported by the remaining UPS system. If the total load exceeds the capacity of the remaining UPS system, it will switch to auto bypass mode.

3

4

5

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

 

 

 

 

UPS1

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

UPS2

LOAD

67-6 Battery Backup Mode (Parallel UPS)

Similar to on battery backup mode for a single UPS system (Section

7-2), except the total connected equipment load is shared by the parallel (1+1) UPS systems.

7

8

9

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

 

 

 

 

UPS1

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

UPS2

LOAD

10

7-7 Auto Bypass Mode (Parallel UPS)

Similar to auto bypass mode for a single UPS system (Section 7-3), except with parallel (1+1) UPS systems.

11

12

13

18

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

 

 

 

 

UPS1

 

CB3

 

 

 

MAIN

CB2

CB1

 

CB4

 

XFMR

 

XFMR

 

 

 

 

 

 

CB5

STS

 

 

 

 

UPS2

LOAD

200803004 93-2793 SU80k manual 4C.indd E18

6/16/2008 1:43:27 PM