Tripp Lite SU80K UPS System Technical Specifications, UPS System Floor Loading Table

Models: SU80K

1 142
Download 142 pages 60.75 Kb
Page 46
Image 46

11 – Specifications

1

2

3

4

5

6

7

8

9

10

11

11-1 UPS System Technical Specifications

 

 

 

Model (Capacity)

SU80K (80kVA/64kW)

Input

Input Voltage

 

120/208V AC, 3Ø, 4-wire + ground, wye

 

 

 

 

 

 

 

Voltage Regulation

 

-25% ~ +20%

 

 

Harmonic Distortion

 

< 5% (Full Load)

 

 

 

 

 

 

 

PFC (Full Load)

 

> 0.99

 

 

Frequency

 

50 / 60 Hz

 

 

Frequency Tolerance

 

45 ~ 65 Hz

 

 

 

 

 

Output

Input Voltage

 

120/208V AC, 3Ø, 4-wire + ground, wye

 

 

 

 

 

 

 

Output Frequency

 

50 / 60 Hz

 

 

 

 

 

 

 

Total Harmonic (Linear Load)

 

3%

 

 

 

 

 

 

 

Voltage Regulation

Static

±1%

 

 

 

 

 

 

 

 

Dynamic

±7% (10% ~ 90% Linear Load)

 

 

 

 

 

 

 

Frequency Regulation

Interior Oscillator

±0.05 Hz

 

 

 

 

 

 

 

 

Synchronized

±5%

 

 

 

 

 

 

 

Overload

 

125% : 10 minutes; 150% : 1 minute

 

 

 

 

Audible Warning

Battery Backup

 

Intermittent

 

 

 

 

 

 

 

UPS Abnormal

 

Continuous

 

 

 

 

 

Display

LED

 

UPS Status: Normal • Bypass • Backup • Fault

 

 

 

 

 

 

 

LCD

 

Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage

 

 

 

 

UPS abnormal messages with intelligent self-diagnosis.

 

 

 

 

Interface

Standard

 

RS-232, Dry Contact

 

 

 

 

 

 

 

Optional

 

SNMPWEBCARD

 

 

 

 

Others

Parallel Redundancy

 

Yes (1+1 for 2 UPS systems of the same type and capacity only.)

 

 

 

 

 

 

 

EPO

 

Standard (Local and Remote)

 

 

 

 

 

 

 

SRAM Event Log

 

500 Records

 

 

 

 

 

 

 

Parameter Configuration

 

Yes

 

 

 

 

 

 

 

Hot Standby Installation

 

Optional

 

 

 

 

 

 

 

Battery Temperature Compensation

Optional

 

 

 

 

 

 

 

Battery Cold-Start

 

Standard

 

 

 

 

Overall

Efficiency

Normal

92%

 

 

 

 

 

 

 

 

ECO

96%

 

 

 

 

 

 

 

Transfer Time

 

0 ms

 

 

 

 

 

 

 

Temperature

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

 

 

Humidity (non-condensing)

 

90%

 

 

Noise (1 m)

 

70 dBA

 

 

Dimensions (Power Module)

Width

520 mm

 

 

 

Depth

1026 mm

 

 

 

Height

1696 mm

 

 

Weight (Power Module)

 

655 kg

 

 

 

 

 

12

13

11-2 UPS System Floor Loading Table

Model

SU80K

Weight

655 kg

 

 

Floor Loading

1228 kg/m2

 

 

11-3 Battery Pack Floor Loading Table

 

BP480V26B

BP480V40C

 

(40 12V batteries;

(40 12V batteries;

Model

26AH each)

40AH each)

Weight

470 kg

700 kg

 

 

 

Floor Loading

1064 kg/m2

1575 kg/m2

 

 

 

46

200803004 93-2793 SU80k manual 4C.indd E46

6/16/2008 1:44:01 PM

Page 46
Image 46
Tripp Lite SU80K UPS System Technical Specifications, UPS System Floor Loading Table, Battery Pack Floor Loading Table