6 – Internal Battery Connection (continued)

1

6-2 Internal Battery Connection Procedure

1 Place the UPS system in bypass (or turn it completely off) and turn off the internal battery circuit breaker switch, located on the rear of the UPS system.

2 Remove the battery access bezels, located on the front of the UPS system.

3 Remove the battery cartridge fuses from each fuse block.

4 Disconnect the blue and white jumper cables attached to each fuse block. Warning: When disconnecting the jumper cables, pull them straight away from the fuse block with even force. Do not wiggle them side-to-side, as this may damage the connector.

5 Remove the fuse block bracket. Note its orientation before removal.