11 – Communications (continued)

1

11-8 Output Dry Contact Interface Detail

The UPS system has six dry contact output connections. These contacts can be normally open or normally closed.

2

Default Messages

3

4

Contact

Message

Description

Pin 1-2

Load on inverter

The UPS system is working normally.

 

 

 

Pin 3-4

Load on auto bypass

The UPS system is in bypass mode.

 

 

 

Pin 5-6

Mains input failure with load on inverter

Utility power is absent (blackout) or abnormal. The UPS system is in battery backup mode.

 

 

 

Pin 7-8

Battery low

The UPS system is in battery backup mode, and battery voltage is lower than 220V.

 

 

 

Pin 9-10

Bypass input abnormal

The bypass input is abnormal (frequency / phase).

 

 

 

Pin 11-12

Battery test failure

The battery voltage is lower than the reference value.

 

 

 

5

6

7

8

9

10

11

12

13

14

 

Optional Messages

 

 

Message

Description

Internal communication failure

Communication with one of the internal components is not normal.

 

 

External parallel communication failure

In a parallel redundancy installation, the parallel communication is not normal.

 

 

Output overload warning/shutdown

The load exceeds the capacity of the UPS system.

 

 

Power module fault shutdown

The UPS system has shut down due to an internal power module failure.

 

 

Power module warning

An internal power module has an error, but the UPS system can still function normally.

 

 

EPO activated

The UPS system’s output is disabled by the emergency power off (EPO) function.

 

 

Load on manual bypass

The UPS system is in manual bypass mode.

 

 

Battery cabinet over temperature warning/shutdown

The temperature of the external battery cabinet is too high.

 

 

Output voltage abnormal

The UPS system’s output voltage is too high or too low.

 

 

Battery need replace

According to the data in the “BAT DATE SETTING”, the UPS system is overdue for battery

 

replacement. (See Section 10-10for more information.)

 

 

Bypass over temperature warning/shutdown

The temperature of the bypass “static transfer switch” is too high.

 

 

Battery ground fault

The battery has a grounding error.

 

 

Bypass static switch fault

The bypass “static transfer switch” is abnormal.

 

 

Note: If you require optional messages to be enabled, contact Tripp Lite.

48

Page 48
Image 48
Tripp Lite SU80KTV, SU60KTV, SU40K owner manual Output Dry Contact Interface Detail, Default Messages, Optional Messages