10 – Display and Configuration (continued)
1
10-4 Status Messages and Diagrams (continued)
•5 The UPS system is operating in online (normal) mode. Connected
2equipment loads will receive battery backup power if the mains (utility or generator) power source fails.
3
5
4•6 The UPS system has switched to battery backup (on battery) mode. Connected equipment loads are receiving battery backup power, and the estimated remaining runtime is shown. Note: The battery parameters must be set correctly in order to receive accurate runtime estimates from the UPS system when it switches to battery
5backup mode. See Section 10-10 for more information.
6•7 The UPS system has switched to battery backup (on battery) mode. Connected equipment loads are still receiving AC power inverted from battery power, but battery power is nearly depleted.
7
8
•8 The UPS system is performing a battery test.
9
10
•9 The UPS system is operating in economy mode, and connected equipment loads are being powered by the bypass source.
11
12
•10 The UPS system is in manual bypass mode in order to allow qualified service personnel to perform maintenance or repair on
13 the UPS system. Connected equipment loads will lose power if the bypass power source fails.
14
6
7
8
9 |
10 |