7 – Wiring (continued)

1

7-7 AC Input/Output Wiring (Single UPS)

1 After de-energizing all input and output (AC and DC) of the UPS

2system, remove the terminal block cover from the UPS system.

3

42 If you did not connect the ground cable in Section 7-6, connect the UPS system’s grounding terminal A to your facility’s earth ground B with a 4 AWG (5.189 mm) ground cable. Keep the ground cable connected at all times after installation.

5

6

3 Remove the UPS system’s front bezel to expose the circuit breakers. First, confirm that the main input circuit breaker switch

Aand the bypass input circuit breaker switch B are both off.

7Second, confirm that the manual bypass circuit breaker switch C is off. Third, confirm that the output circuit breaker switch D is off.

8

 

 

 

 

 

 

4

Confirm the phase of each cable, then connect the cables according

9

 

 

to the UPS system terminal block diagram in Section 7-3. See

 

 

Section 7-5for cable size requirements. Cabling should be

 

 

 

 

 

 

protected by flexible conduit and routed through the appropriate

 

 

 

knockouts in the terminal block cover. Warning: Observe proper

 

 

 

 

phase by connecting R to R, S to S, T to T and N to N. Failure

10

 

 

to observe proper phase will damage the UPS system and

 

 

create a risk of personal injury and property damage.

 

 

 

 

 

 

 

 

 

 

 