7 – Wiring (continued)
1
7-4 External Battery Cabinet Wiring Diagrams (continued)
2 |
|
|
| Q3 |
|
|
|
| |
3 |
|
|
|
|
XFMR |
|
|
| XFMR |
Q2 | Q1 |
|
| Q4 |
MAININPUT | AC/DC | DC/AC | OUTPUT | |
4 |
|
|
|
|
UPS |
|
|
|
|
|
| B+N B- |
|
|
5 |
|
|
|
|
B+ | 12V, 20 Batteries | N | 12V, 20 Batteries | B- |
6 |
|
|
|
|
External Battery Cabinet
B Cabinet: 26AH per Battery
C Cabinet: 40AH per Battery
77-5 Electrical and Cable Data
|
|
|
| Input and Output | Battery | Input and Output | Battery |
8 |
|
|
| ||||
| Model | Input/Output | Breaker Size | Fuse Size | Cable Size | Cable Size | |
|
| SU40K | 120/208V AC, 3O, | 150A | 120A | 1/0 AWG | 6 AWG |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
| SU60K | 120/208V AC, 3O, | 225A | 160A | 4/0 AWG | 4 AWG |
9 |
|
|
|
|
|
| |
| SU60KTV | 277/480V AC, 3O, | 100A | 160A | 4 AWG | 4 AWG | |
|
| ||||||
|
|
|
|
|
|
| |
|
| SU80KTV | 277/480V AC, 3O, | 125A | 220A | 2 AWG | 2 AWG |
|
|
|
|
|
|
|