GEN AUTO START SETUP (12) MENU HEADING

MENU SYSTEM

GEN AUTO START SETUP (12) MENU HEADING

Set Load Start

 

amps AC

33

All models

Range: 00 to 63

Sets the AC load current that will initiate the automatic generator control system when the current remains above this setting continuously for the LOAD START DELAY MIN period.

Set Load Start

 

delay min

05.0

All models

Range: 00.0 to 25.5

Sets the time delay period that will initiate automatic generator control system when the current remains above the LOAD START AMPS AC setting continuously for this time period.

Set Load Stop

 

delays min

05.0

All models

Range: 00.0 to 25.5

Sets the amount of time that the automatic generator will continue to run after the load current (determined by the LOAD AMPS AC meter) decreases below the LOAD START AMPS AC setting.

Set 24 hr start

Set 24 hr start

Set 24 hr start

volts DC

12.3

12 VDC models

Range: 05.0 to 16.5

volts DC

24.6

24 VDC models

Range: 10.0 to 35.5

volts DC

49.2

48 VDC models

Range: 20.0 to 71.0

Sets the battery voltage that will initiate the automatic generator control system if the voltage remains below this setting continuously for 24 hours. This setting is not temperature compensated. This 24-hour start is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.

Set 2

hr

start

volts

DC

11.8

12 VDC models

Range: 05.0 to 16.5

Set 2

hr

start

volts

DC

23.6

24 VDC models

Range: 10.0 to 35.5

Set 2

hr

start

volts

DC

47.2

48 VDC models

Range: 20.0 to 71.0

Sets the battery voltage that will initiate the automatic generator control system if the voltage remains below this setting continuously for 2 hours. This setting is not temperature compensated. This 2-hour start is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.

Set 15 min start

volts DC

11.3

12 VDC models

Range: 05.0 to 16.5

Set 15 min start

volts DC

22.6

24 VDC models

Range: 10.0 to 35.5

Set 15 min start

volts DC

45.2

48 VDC models

Range: 20.0 to 71.0

Sets the battery voltage that will initiate the automatic generator control system if the voltage remains below this setting continuously for 15 minutes. This setting is not temperature compensated. This 15- minute start is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.

Read 30 sec LBCO

start VDC

11.0

12 VDC models

Range: 05.0 to 16.5

Read 30 sec LBCO

start VDC

22.0

24 VDC models

Range: 10.0 to 35.5

Read 30 sec LBCO

start VDC

44.0

48 VDC models

Range: 20.0 to 71.0

Displays the battery voltage setting that will initiate the automatic generator control system if the voltage remains below the setting continuously for 30 seconds. This setting is not temperature compensated. This display is linked and is adjusted by the SET LOW BATTERY CUT OUT VDC menu item setting under the INVERTER SETUP (9) menu heading. This 30-second start will attempt to start the auto start generator even if the QUIET TIME under GENERATOR TIMER (7) is enabled.

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page

49

Page 57
Image 57
Xantrex Technology 120 VAC/60 owner manual GEN AUTO START SETUP 12 MENU HEADING, Menu System, Page