APPENDIX

SIZE

14

12

10

8

6

4

3

2

1

1/0

DIAMETE

.073

.072

.115

.146

.184

.235

.281

.295

.335

.380

R

 

 

 

 

 

 

 

 

 

 

SIZE

2/0

3/0

4/0

250 MCM

300 MCM

350 MCM

400 MCM

500 MCM

DIAMETE

.420

.475

.530

.580

.635

.690

.730

.820

R

 

 

 

 

 

 

 

 

Note: Sizes shown are for the conductor – do not include any insulation when determining your wire size.

Figure 40, AWG Wire Size

Table 11, Minimum Recommended Battery Cable Size vs. Cable Length

INVERTER

MODEL

TYPICAL

DC

AMPS1

NEC

AMPS2

1 TO 3 FEET

ONE WAY

3 TO 5 FT ONE WAY

5 TO 10 FT ONE WAY

SW2512

SW2612E

SW3024E or J

SW4024 or W, K

SW3048E or J

SW4048 or K

SW4548E or A

SW5548

267Amps

278Amps

160Amps

214Amps 80 Amps

107Amps

120Amps

147Amps

334 Amps

#4/0 AWG/107 mm2

348 Amps

#4/0 AWG/107 mm2

201 Amps

#4/0 AWG/107 mm2

267 Amps

#4/0 AWG/107 mm2

100 Amps

#2/0 AWG/67.4 mm2

134 Amps

#2/0 AWG/67.4 mm2

150 Amps

#2/0 AWG/67.4 mm2

184 Amps

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#2/0 AWG/67.4 mm2

#2/0 AWG/67.4 mm2

#2/0 AWG/67.4 mm2

#4/0 AWG/107 mm2

Not Recommended

Not Recommended

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

#4/0 AWG/107 mm2

1TYPICAL DC AMPS is based on Low Battery Voltage with an efficiency of 85%.

2NEC AMPS is based on Low Battery Voltage, an efficiency of 85%, and a 125% NEC de-rating.

CABLE SIZE

REQUIRED

#2 AWG

#2/0 (00) AWG

#4/0 (0000) AWG

Table 12, Battery Cable to Maximum Breaker/Fuse Size

RATING IN

MAXIMUM

RATING IN

CONDUIT

BREAKER SIZE

“FREE AIR”

115 amps

125 amps*

170 amps

175 amps

175 amps

265 amps

230 amps

250 amps*

360 amps

MAXIMUM FUSE SIZE

175amps*

300amps*

400amps*

*The NEC allows rounding up to the next standard fuse size from the cable rating, i.e. 150-amp cable size rounds up to a standard 175-amp size.

The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway. Cables enclosed in raceways or conduits have substantially lower continuous current carrying ability due to heating factors.