MENU SYSTEM
SETUP MENU MAP
The SETUP MENU provides all the controls and settings needed when installing or adjusting the system. To access the SETUP MENU, press both the red ON/OFF MENU and green GEN MENU buttons on the Control Panel at the same time. To exit the SETUP MENU, press the red ON/OFF MENU button or press the down MENU HEADING button until you reach the USER MENU (menu headings
MENU HEADINGS
Inverter Setup |
| Battery Charging |
| AC Inputs |
|
| Gen Auto Start |
|
| Gen starting |
|
| Auxiliary Relays | |
9 |
| 10 |
|
| 11 |
| setup | 12 |
| details | 13 |
| R9 R10 R11 | 14 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MENU ITEMS
Set Grid Usage
FLT SELL SLT LBX
Set Low battery cut out VDC 11.0
Set LBCO delay
minutes | 10 |
| |
Set Low battery | |
cut in VDC | 13.0 |
| |
Set High battery | |
cut out VDC | 16.0 |
|
|
Set search |
|
watts | 48 |
|
|
Set search |
|
spacing | 59 |
Set Bulk |
|
volts DC | 14.4 |
| |
Set Absorption | |
time h:m | 02:00 |
|
|
Set Float |
|
volts DC | 13.4 |
| |
Set Equalize | |
volts DC | 14.4 |
| |
Set Equalize | |
time h:m | 02:00 |
| |
Set Max Charge | |
amps AC | 20 |
|
|
Set Temp Comp
LeadAcid NiCad
Set Grid (AC1)
amps AC | 60 |
|
|
Set Gen (AC2) |
|
amps AC | 30 |
| |
Set Input lower | |
limit VAC | 108 |
| |
Set Input upper | |
limit VAC | 132 |
Set Load Start
amp AC | 20 |
| |
Set Load Start | |
delay min | 5.0 |
| |
Set Load Stop | |
delay min | 5.0 |
| |
Set 24 hr start | |
volts DC | 12.3 |
| |
Set 2 hr start | |
volts DC | 11.8 |
| |
Set 15 min start | |
volts DC | 11.3 |
| |
Read LBCO 30 sec | |
start VDC | 11.0 |
| |
Set Exercise | |
period days | 30 |
| |
Set Maximum run | |
time h:m | 08:00 |
Set Max Run time
to 0 to defeat.
Set Exercise to 0
to defeat.
See menu 9 to
to set LBCO.
Set RY7 Function GlowStop Run
Set Gen warmup
seconds 60
Set Pre Crank
seconds 10
Set Max Cranking
seconds 10
Set Post Crank
seconds 30
Set Relay 9
volts DC | 14.5 |
| |
R9 Hysteresis | |
volts DC | 01.0 |
| |
Set Relay 10 | |
volts DC | 14.8 |
| |
R10 Hysteresis | |
volts DC | 01.0 |
| |
Set Relay 11 | |
volts DC | 15.0 |
| |
R11 Hysteresis | |
volts DC | 01.0 |
Close on batt > | |
setpoint. |
|
Open on | batt < |
setpoint - Hys
Relays have 2
second delay on
Close, 0.1 sec
delay on open
|
| Bulk Charge |
|
| Low Battery |
|
| Battery Selling |
| Grid Usage Timer |
| Information file |
| End Setup Menu | |||
|
| Trigger Timer 15 |
| Transfer (LBX) 16 |
|
| 17 |
|
| 18 |
| battery | 19 |
| 20 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| Set Start Bulk |
| Set Low Battery |
| Set Battery Sell |
| Start Charge |
| Batt temp comp |
|
|
| ||||
|
| time | 00:00 |
| TransferVDC | 11.3 |
| volts DC | 13.4 |
| time | 21:00 |
| changes battery |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| To disable timer |
| Set Low battery |
| Set Max Sell |
|
| End Charge |
|
| voltage reading |
|
|
| ||
|
| set to 00:00 |
|
| cut in VDC | 13.0 |
| amps AC | 30 |
| time | 21:00 |
| away from actual |
|
|
|
|
| If grid timer |
|
| See menu 9 to |
|
| See menu 9 to |
|
| After Start |
|
| HBCO resets at: |
|
|
|
|
| active set bulk |
| enable LBX mode. |
| enable SELL mode. |
| Charge time: |
|
| 6v/48, 3v/24 and |
|
|
| |||
|
| time after start |
| Make sure LBX is |
| Make sure LBX is |
| SELL mode |
|
| 1.5v/12v under |
|
|
| |||
|
| charge time. |
|
| above LBCO volts. |
| above LBCO volts. |
| charges battery. |
| HBCO. |
|
|
| |||
|
| In SLT mode don’t |
|
|
|
|
|
|
| FLT mode |
|
| LowBattTransfer |
|
|
| |
|
| disable this |
|
|
|
|
|
|
|
| charges battery |
| used in LBX, FLT |
|
|
| |
|
| timer. It is the |
|
|
|
|
|
|
| After End Charge |
| Modes only. Goes |
|
|
| ||
|
| daily chg time. |
|
|
|
|
|
|
| time: |
|
| back to battery |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| SELL mode sells |
| at LowBattCutIn |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| battery to AC1. |
| (aka LBCI). |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| FLT mode drops |
| For LBX mode set |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| AC1 and inverts |
| below LBCI so |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Timer on when |
|
| charger won’t |
|
|
|
|
|
|
|
|
|
|
|
|
|
| start < > end; |
| cycle batteries |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| timer off when |
| up and down and |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| start = end |
|
| set LBCO below. |
|
|
|
Sell and float
modes use timer
SLT and LBX mode ignore timer