OPERATION
INVERTER MODE
BATTERYDC
INVERTER
AC |
| AC LOADS |
|
IN BRIEF
The inverter makes a stepped approximation to a sine wave. The number of steps typically varies from 34 to 52 per cycle. Lower battery voltage and/or higher output power level increases the number of steps. Higher battery voltage decreases the number of steps. Distortion varies from 3% to 5%. The inverter is able to control the AC output voltage, allowing the inverter to also sell power into a utility grid or assist during the operation of heavy loads by operating in parallel with another AC power source such as a engine powered generator.
SEARCH MODE CONTROL
An automatic search mode circuit is available to minimize the power draw of the inverter when no loads are being operated. This reduces the power consumption from 16 watts with no load to less than 1 watt (when using the default settings). To do this, the output is reduced to pulses of a single AC cycle with an adjustable delay between pulses. These pulses are used to detect the presence of a load. When a load is detected, the inverter’s output goes to full 120 VAC output. The sensitivity of the detection circuit and the spacing of the pulses are user adjustable using the Control Panel.
This feature can save a considerable amount of power, particularly in smaller systems that do not have loads operating all of the time. In larger systems, this feature may not result in as much savings. If continuous operation of an AC load is required (such as when powering a microwave clock, VCR timer, computer, or fax machine), then using the search mode is not recommended.
To enable the search mode: Select SRCH mode from the SET INVERTER menu item, accessible by pushing the red ON/OFF MENU button. Pressing the red ON/OFF MENU button can also access the SRCH mode. It is also located as the first menu item under the INVERTER MODE (1) menu heading. Pressing the red ON/OFF MENU button again will move the cursor one position to the right. The SET POINT buttons can also be used to move the cursor right or left. To disable the search mode, select ON from the SET INVERTER menu item.
Successful operation of the system utilizing the search mode requires some initial tuning of the search mode settings to match the loads connected in the system. If the loads change significantly,
SETTING SEARCH MODE WATTS
The search mode is user adjustable to allow
Example: With the SEARCH WATTS setting at 32, a
When in the search mode, the yellow INVERT LED will blink slowly and the inverter will make a ticking sound. At full output voltage, the yellow INVERT LED will stay on and the inverter will make a steady humming sound. When the inverter is used as an uninterruptible power supply, the search mode should be defeated.