CONTROLS, INDICATORS AND COMPONENTS
AC SIDE
Figure 4 shows the components located on the AC side of the inverter. The removable AC Access Panels cover and protect the Internal Components and Indicators, such as the AC Terminal Block, BTS Connection, LED status indicators (for the AC1 and Gen Control relays) and the Aux and Gen Control relay terminals. Refer to the INSTALLATION section beginning on page 15, for all wiring connections.
Identification
Label
Remote
Port
Stacking
Port
Inverter/ |
Charger |
Circuit Breaker |
Knockouts |
(Also On Side} |
Three |
Removable |
Access Panel |
(One Panel on |
Side) |
Figure 4, AC Side
REMOTE PORT
The SW Series Inverter/Charger can be controlled remotely from the unit by plugging in a Sine wave Remote Control (SWRC) or Sine wave Communications Adapter (SWCA).
The SWRC remote control is a full function, programmable remote control with backlit LCD which duplicates the functions of the integral Control Panel.
The SWCA serial communications interface adapter allows for remote setup, adjustment, monitoring and troubleshooting of SW Series Inverter/Chargers from a personal computer and allows modem access monitoring over long distances.
See the APPENDIX, OPTIONS section, starting on page 128, for a complete description of the SWRC Remote Control and SWCA Serial Communications Adapter.
STACKING PORT
The stacking port allows multiple SW Series Inverter/Chargers to be used in the same system. The inverters can be used in a “SERIES” configuration to operate 240 Vac loads and to connect to 120/240 Vac power systems. A series stacking interface cable (SWI) is required to connect the series stacking ports of the inverters. This port is also used to connect two units in a “PARALLEL” configuration. The parallel stacking interface cable (SWI/PAR) allows two inverters to be connected to provide twice the continuous and surge capability at the same AC voltage. See the USING MULTIPLE INVERTERS section on page 95 for more information.
INVERTER/CHARGER CIRCUIT BREAKER
This circuit breaker protects the unit’s internal wiring while the unit is inverting or charging. It is not used for the