Xantrex Technology 120 VAC/60 Close on batt setpoint. Open on batt setpoint - hys, Menu System

Models: 120 VAC/60

1 152
Download 152 pages 20.65 Kb
Page 60
Image 60
Close on batt > setpoint. Open on batt < setpoint – hys.

MENU SYSTEM

Set Relay 9

 

volts DC

14.5

12 VDC Models

Range: 05.0 to 17.6

Set Relay 9

 

volts DC

29.0

24 VDC Models

Range: 10.0 to 35.5

Set Relay 9

 

volts DC

58.0

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 9. This setting is compensated for the battery temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This allows fast response to rapid voltage changes in the system.

R9 Hysteresis

 

volts DC

01.0

12 VDC Models

Range: 00.1 to 12.8

R9 Hysteresis

 

volts DC

02.0

24 VDC Models

Range: 00.1 to 12.8

R9 Hysteresis

 

volts DC

04.0

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 9. There is an intentional 2-second time delay to reduce cycling.

Set Relay 10

 

volts DC

14.8

12 VDC Models

Range: 05.0 to 17.6

Set Relay 10

 

volts DC

29.5

24 VDC Models

Range: 10.0 to 35.5

Set Relay 10

 

volts DC

59.0

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 10. This setting is compensated for the battery temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This allows fast response to rapid voltage changes in the system.

R10 Hysteresis

 

volts DC

01.0

12 VDC Models

Range: 00.1 to 12.8

R10 Hysteresis

 

volts DC

02.0

24 VDC Models

Range: 00.1 to 12.8

R10 Hysteresis

 

volts DC

04.0

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 10. There is an intentional 2-second time delay to reduce cycling.

Set Relay 11

 

volts DC

15.0

12 VDC Models

Range: 05.0 to 17.6

Set Relay 11

 

volts DC

30.0

24 VDC Models

Range: 10.0 to 35.5

Set Relay 11

 

volts DC

60.0

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 11. This setting is compensated for the battery temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This allows fast response to rapid voltage changes in the system.

R11 Hysteresis

 

volts DC

01.0

12 VDC Models

Range: 00.1 to 12.8

R11 Hysteresis

 

volts DC

02.0

24 VDC Models

Range: 00.1 to 12.8

R11 Hysteresis

 

volts DC

04.0

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 11. There is an intentional 2-second time delay to reduce cycling.

INFORMATION DISPLAY

The following information is displayed as additional Menu Items.

Close on batt > setpoint. Open on batt < setpoint – hys.

Relays have 2 seconds delay on close, 0.1 sec delay on open.

Page

52

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page 60
Image 60
Xantrex Technology 120 VAC/60 Close on batt setpoint. Open on batt setpoint - hys, Menu System, Page, Information Display