Xantrex Technology 120 VAC/60 Ac In, AC Input/Output Power Connection, Ac Out, Ac Connections

Models: 120 VAC/60

1 152
Download 152 pages 20.65 Kb
Page 27
Image 27
AC IN 2

INSTALLATION

Note: The three neutral terminals are common to each other and can be used in any combination or order. In a residential application, it is often easier to only connect one AC neutral wire to the inverter and make the other neutral connections at a central point such as in the AC load center, etc. In mobile installations, the AC system must have the neutral physically isolated from the ground throughout the load distribution powered by the inverter. The SW Series Inverter/Charger does not include neutral to ground switching for the AC electrical system. This must be done externally from the inverter. See the NEUTRAL- TO-GROUND BOND SWITCHING (RV AND MARINE APPLICATIONS) section on page 27 for more information.

AC Terminal Block

(TB1)

 

1a

1b

 

2a

2b

AC IN 2

 

 

From

3a

3b

Generator Power

 

 

 

4a

4b

 

5a

5b

 

6a

6b

Figure 9, AC Input/Output Power Connection

AC IN 1

From

Utility Power

AC OUT

To

AC Loads

Before making any AC connections, make sure that the inverter is disconnected from the battery (or battery bank). Feed the wires through conduit fittings located on the left side or left bottom side of the inverter. (Note: Conduit fittings must be purchased separately and are required by code to comply with residential and commercial installations).

The AC wiring both in and out of the inverter must also be protected from short circuits and overloads by a fuse or circuit breaker. Consult the NEC or your local code for more information and for other wire sizes. Table 13 on page 132 gives suggestions for wire sizing. Follow the wiring guide on the circuit board inside the cover plate (see Figure 9, above). Connect the AC wiring as follows (from front to back when wall mounted):

Table 1, AC Input and Output Wiring Connections

AC CONNECTIONS

AC HOT IN 1

NEUTRAL IN 1

AC HOT IN 2

NEUTRAL IN 2

AC HOT OUT

NEUTRAL OUT

AC TERMINAL BLOCK #

1b

3b

2b

4b

6b

5b

WIRE COLOR

Black (Hot)

White (Neutral)

Black (Hot)

White (Neutral)

Black or Red (Hot)

White (Neutral)

PURPOSE

Utility Power

Utility Power

Generator

Generator

AC Loads

AC Loads

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page

19

Page 27
Image 27
Xantrex Technology 120 VAC/60 Ac In, AC Input/Output Power Connection, Ac Out, AC Input and Output Wiring Connections