Advanced Settings
Breaker Derating | To change the breaker derating from the Advanced Settings screen: | ||||||
According to NEC standards, the total current of all loads in a branch circuit | FSPM 00: Status |
|
| FSPM 00: Status |
| ||
should be limited to 80% of its circuit breaker rating to ensure that a | L2 Amps |
| 0.0A | Batt Voltage |
| 12.8V | |
combination of continuous and | Batt Voltage |
| 12.8V | Circuit Status |
| ||
tripping the circuit breaker. Freedom Sequence applies this conservative | Circuit Status |
|
| Config |
|
| |
Config |
|
| Advanced Settings |
| |||
standard in its load shedding logic. However, when all loads (continuous |
|
|
| ||||
|
|
|
|
|
| ||
and |
|
|
|
|
|
| |
appropriately sized, listed, and rated to handle 100% of their rating, |
|
|
|
|
|
| |
derating the load capacity is not necessary and 100% capacity can be | 1 Press all three buttons to | 3 Press button. | 2 Scroll down to select | ||||
utilized. | |||||||
enable Advanced Settings. |
|
| Advanced Settings. | ||||
IMPORTANT: Appliances and circuit breakers that are 100% rated will | FSPM 00: Advanced Settings | FSPM 00: Advanced Settings | |||||
BKR Derating |
| [Enabled] | BKR Derating | [*Enabled] | |||
|
| ||||||
have a listing on their product label similar to “Suitable For Use On Single- | GEN BKR Rating |
| [30.0A] | GEN BKR Rating | [30.0A] | ||
GEN Warmup Delay |
| [0sec] | GEN Warmup Delay | [*0sec] | |||
Phase ~AC circuits. For 100% Application.” | Connect Seq Delay | [10sec] | Connect Seq Delay | [10sec] | |||
The option to disable breaker derating is available by changing the default |
|
|
|
|
|
| |
Enabled to Disabled in Advanced Settings. | 5 Press to change | 4 Scroll down | 7 Press to | 6 Scroll up or down | |||
For more information on how AC load shedding works, see “AC Load | the setting. |
|
| confirm the | to choose a value. | ||
FSPM 00: Advanced Settings | selected |
|
| ||||
Shedding” on page 34. | value. |
|
| ||||
BKR Derating | [Disabled] |
|
| ||||
|
|
|
| ||||
| GEN BKR Rating |
| [30.0A] |
|
|
| |
| GEN Warmup Delay |
| [2sec] |
|
|
| |
| Connect Seq Delay | [10sec] |
|
|
|
|