FSequence IPM Owners Guide.book Page 23 Thursday, October 6, 2011 3:33 PM

 

Advanced Settings

Generator Breaker Rating

To change the generator warmup delay from the Advanced Settings

 

screen:

The generator breaker rating can be set between 5 to 50 amps. By default, the setting is set to 30 amps.

Generator Warmup Delay

The Freedom Sequence power manager applies a generator warmup delay timer (GEN Warmup Delay) to allow any Xanbus-controlled generator a chance to warmup after starting. This delay is similar to warming up a car engine before driving.

The generator warmup delay timer, which can be modified by changing the GEN Warmup Delay setting, is set by default to zero second. The generator warmup delay timer value can be set between 1 to 240 seconds.

NOTE: It is recommended to set the GEN Warmup Delay value to match either the transfer switch delay timer or the generator’s warmup delay timer specified by the manufacturer of the device. Consult the device’s user guide under its specifications or contact the manufacturer for information on the timer rating. Choose a delay that is highest between these two devices.

FSPM 00: Status

L2 Amps

0.0A

Batt Voltage

12.8V

Circuit Status

 

 

 

 

Config

 

1 Press all three buttons to enable Advanced Settings.

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[0sec]

Connect Seq Delay

[10sec]

AC Disc Priority

[2]

5 Press to change

4 Scroll down

the setting.

 

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[2sec]

Connect Seq Delay

[10sec]

AC Disc Priority

[2]

FSPM 00: Status

Batt Voltage

12.8V

Circuit Status

Config

Advanced Settings

3 Press button. 2 Scroll down to select Advanced Settings.

FSPM 00: Advanced Settings

GEN BKR

Rating

[30.0A]

GEN Warmup Delay

[*0sec]

Connect

Seq Delay

[10sec]

AC Disc

Priority

[2]

7 Press to 6 Scroll up or down confirm the to choose a value. selected

value.

 

 

975-0593-01-01

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 33
Image 33
Xantrex Technology 809-0912 manual Generator Breaker Rating, Generator Warmup Delay, Screen, GEN Warmup Delay, 0sec